Ascend Single Phase Charger Operation Manual
Pressing this button when the Charger is in Equalize Mode will return the Charger to Float Mode.
Pressing this button when in Float Mode will automatically go to the menu for the user to put the
Charger in Equalize Mode. The data log will store each Float or Equalize event.

6.6.3. Configuring Alarm Set Points

Alarm set points can be adjusted during operation via the Setup -> Alarm setup screen. Each alarm will
list the Set Point and delay for the alarm. Depending on the alarm there may only be one of the
variables for the alarms. See 7.5. Alarm Indications and 7.6. Optional Alarms for set up limits.
Figure 21: Alarm Setup Screen
Pressing an alarm button allows the set point and/or delay to be modified.
The Alarm set points can be reset to their factory defaults, by going to Setup -> Reset Data -> Alarm Set
Points screen and pressing Reset. You can also cancel this operation.

6.6.4. Current Limit Adjustment

To change the Charger output current limit, go to the Setup -> Adjustments -> Output Current Limit
Menu. Set the desired current limit value using the keypad, range is 50% to 100% of rated output. Press
Save to save the new value and exit. The new current limit value will be in effect.
6.6.5. Date & Time
To change the date and time go to the Setup -> Date & Time screen.
If the Communications Package Option (187) is provided a Coordinated Universal Time (UTC) Offset
Button is available to allow the UTC offset to be modified to reflect the time zone.
The NTP Button allows the Network Time Protocol to be enabled or disabled and the IP address of the
NTP server to be changed. If NTP is enabled, the user will not be able to change the date or time
manually.