Ametek ASCEND Series Operation Manual page 24

Single phase modular charger
Table of Contents

Advertisement

Ascend Single Phase Charger Operation Manual
Alarm Silence Button
The Alarm Silence Button
is enabled when the alarm buzzer is active. When it is pressed, the alarm
buzzer will turn off and stay off for at least 60 seconds, even if a new alarm becomes active.
Lock/Unlock Toggle Button
This icon identifies if the setup menu password has been entered. Pressing this button while it is locked
navigates to the Enter Password Screen. Pressing it while unlocked
logs the user out. The user will
automatically be logged out when the LCD goes to sleep.
Battery Control Button
The Battery Control Button displays the status of the Charger output to the battery. A green battery
indicates the Charge is in Float Mode. An amber battery
indicates the Charge is in Equalize mode.
Pressing this button when the Charger is in Equalize Mode will return the Charger to Float Mode.
Pressing this button when in Float Mode will automatically go to the menu for the user to put the
Charger in Equalize Mode.
A red battery
signifies the battery is discharging.
A gray battery
indicates the communication between the Display and Charger modules has failed
and the Battery current measurement is not included in the system.
Alarm Status Button
The Alarm Status Button displays the current number of active and latched* alarms. If an alarm is active
or latched the button will display the number of alarms
, if no alarms are present the indicator is
green. Pressing this button will automatically display the Active Alarms Window.
*Requires the Latching Alarms enabled, see 7.4.7. Latching Alarms.
95-100167, Rev A