Ascend Single Phase Charger Operation Manual

7.7.6. DNP3 Communications

DNP3 optional (# 234) communications provides access to system voltages, currents, and alarm status.
There is no control provided via DNP3. A Moxa MGate 5109 Industrial protocol gateway is used to
convert Modbus RTU to DNP3.
Configure the DNP3 IP address by connecting a Web enabled browser to the gateway and follow the
instructions below.
1. Type the IP address of the device into the search bar of your choice of browser (default is
192.168.127.254)
2. Sign into device (default: username-admin, password-moxa)
3. Open the tab labeled "Network Settings"
4. Change IP and Netmask as needed.
95-100167, Rev A
Figure 32: Network Settings Screen – SNMP Settings
46