Exercise
Enter the menu
Setting the decimal point 1. Keep stepping by pressing the ▲ button as long as you
Setting the physical
value assigned to 4 mA
20180614-V0

10.7. Setting up the instrument (Example)

There is a pressure transmitter with a measurement range
of 5-150 bar corresponds to 4-20 mA.
Let the settings of DT9000 N be the following:
Number of decimals: 2.
The physical value assigned for the 4 mA current: 5.00
The physical value assigned for the 20 mA current: 150.00
The leader zeros are not displayed.
Enter the menu by using a Supervisor Code.
The way the code should be typing in is described in
Chapter 7.1. Typing the code in. You see on the display:

.
see this menu item:
2. Enter the menu item by pressing the ENTER button.

3. You see this
blinking.
4. Set the number of decimals to two by pressing the ▲
button:

.
5. Press the MENU button, to exit from the menu item, and

you see this:
1. Pressing the ▲ button keep stepping as long as you see

this menu item:
2. Enter the menu item by pressing the ENTER button.
3. Pressing the ▲ button you can increase the value of the
blinking number:
4. Pressing the ► button you can select the next digit.

5. Set the value
6. Press the MENU button, to exit from the menu item, and

you see this:

.
on the display. The mnemonic is
.
.
.
.