10.3. Setting up the instrument (example)

It is an additional example for Chapter 7. Setting-up. It
helps to understand the setting of values through a practical
example. The steps of the whole setting you will find in
Chapter 7..
There is a AC Voltage Meter with 250 VAC input range. The
voltage value in the power network 0-1000 VAC, voltage
transformer ratio: UX = 4.
The DT4240 xx xx xx xx have 4-20 mA analog output option
Min value: 0 VAC - 4 mA, max value 1000 VAC - 20 mA
In a case of U > 500 VAC, the limit No.1 should be close.
The DT4240 xx xx xx xx parameter settings:
The voltage transformer ratio: UX = 4.
The physical value assigned for the 4 mA current output:
0000.0 VAC.
The physical value assigned for the 20 mA current output:
1000.0 VAC.
The leader zeros are not displayed

03. UX =

06.NUL =
10. L1: L1.SET =
the displayed value > limit value)
10.L1: L1.L:LI =
10. L1: L1.HYS =

14. ANA =

15. A.S.L =

16. A.S.H =
VAC)
(UX = 4)
(disabling the leader zeros)

(the limit output is switch on, if

(limit value 500.0 VAC)

(hysteresys 0.0 VAC)
(4-20 mA analog output)
(analog output 4 mA = 0.0 VAC)
(analog output 20 mA = 1000.0
DT4240 xx xx xx xx