Preventive maintenance,
Tasks,
continued
36
continued
Accessory
Illustration
Hot spot
sensor
Smoke alarm
cable
Smoke alarm
cable with
hot spot
sensor
Smoke
detector
Humidity
controller
Description
This is an extra temperature
sensor to be placed in the critical
spot of the shelter. The operation
of the climate unit will then be
controlled in accordance with the
highest value of either the return
air or hot spot sensor.
Same as the above, inclusive
SUB-D connector
Smoke alarm with two terminal
ends for the smoke alarm
connected together with a terminal
block to establish a normally
closed setting for this function.
The other end of the cable has a
male DUB-D 25W connector
mounted.
Hot spot senor and 2 free smoke
alarm wires supplied with terminal
ends, 10 m.
The two terminal ends for the
smoke alarm are connected
together with a terminal block to
establish a normally closed setting
for this function.
The other end of the cable has a
male SUB-D 25W connector
mounted.
The smoke alarm will detect any
small amount of smoke in the
enclosure air. In case of a smoke
alarm the climate unit will close
the damper (if fitted) and stop the
unit, so that a fire will not be feed
by more fresh air.
Hygrostat with adjustable setting
of the maximum allowed % RH to
override the free cooling and close
the damper.
Part no.
016364
016363
017275
016895
016362
016361
Continued overleaf