The table below shows the most important electrical features of the Silencio. Please
Electrical data
note that the relay and the cable dimensions are Dantherm Air Handling
recommendations. Local regulations must always be observed.
Attention!
Dantherm Air Handling recommend using 16 Amp circuit breakers for both AC and DC
power supply and 2.5 mm
circuit breakers for AC power, and 20 Amp circuit breakers for DC power supply and
2.5 mm
Voltage supply, AC
Voltage supply, 48 V DC
Frequency
Power input
Compressor, maximum
Compressor, nominal
Locked rotor
Power consumption AC
Power consumption DC
Current nominal
2
cables for Silencio 600. It is recommended using 16 Amp
2
cables for Silencio 800, 1000 and 1400.
Specification
Three phase +N +Ground
+ / -
Nominal (tolerance ± 2 Hz)
Compressor at nominal
operation (ARI conditions)
Ambient 35 °C
Return 35 °C
Max. operating current for
compressor
Nominal operating current
for compressor (ARI
conditions)
Max. starting current
All fans nominal speed
All fans nominal speed
1)
All fans nominal speed
Designation
Silencio 600:
Silencio 800:
Silencio 1000:
Silencio 1400:
Silencio 600:
Silencio 800:
Silencio 1000:
Silencio 1400:
Silencio 600:
Silencio 800:
Silencio 1000:
Silencio 1400:
Silencio 600:
Silencio 800:
Silencio 1000, AC:
Silencio 1400, AC:
Silencio 600:
Silencio 800:
Silencio 1000:
Silencio 1400:
Silencio 600:
Silencio 800:
Silencio 1000:
Silencio 1400:
Silencio 600
Silencio 800
Silencio 1000
Silencio 1400
Value
400 V AC ± 10 %
36-56 V DC
50 Hz
2900 W
3340 W
4590 W
7020 W
AC
6.0 A
6.0 A
8.0 A
12.0 A
4.2 A
4.2 A
5.9 A
7.8 A
37.5 A
37.5 A
55.0 A
73.0 A
2780 W
2700 W
3750 W
6200 W
120 W
640 W
840 W
820 W
AC
DC
4.2 A
2.6 A
4.2 A
13.3 A
5.9 A
17.5 A
7.8 A
17.5 A
Continued overleaf