TTF300 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF300-EN REV. I
3 Use in potentially explosive atmospheres in accordance with cFMus, FM
and CSA
Note
Further information on the approval of devices for use in potentially explosive atmospheres can be found in the explosion
protection test certificates (at www.abb.com/temperature).
Depending on the design, a specific marking in accordance with FM, CSA or cFMus applies.
a

Transmitter Ex marking cFMus

cFMus Intrinsically Safe
Model TTF300-L1H for USA or TTF300-R1H for Canada
From HW-Rev.: 02.00
Control Drawing
IS Class I,II,III, Div. 1,2 Group ABCDEFG T6,T4
Zone 0 AEx/Ex ia IIC T6...T1 Ga
Zone 1 AEx/Ex [ia Ga] ib IIC T6...T1 Gb
Zone 1 AEx/Ex ib IIC T6...T1 Gb / [AEx/Ex ia Da] IIIC
cFMus Non-Incendive
Model TTF300-L2H for USA or TTF300-R2H for Canada
From HW-Rev.: 02.00
Control Drawing
NI Class I,II,III Div. 2 Group ABCDEFG T6,T4
Zone 2 AEx/Ex nA IIC T6...T1 Gc
Zone 2 AEx/Ex ec IIC T6...T1 Gc
cFMus Explosion Proof
Model TTF300-L3H for USA or TTF300-R3H for Canada
From HW-Rev.: 02.00
Control Drawing
XP Class I, Div 1,2 Group ABCD T6,T4 for Conduit Um ≤ 42VDC 32mA fused
DIP Class II, Div 1,2 Group EFG T6,T4 Um ≤ 42VDC 32mA fused
XP/IS Class I Div 1,2 GP ABCD T6,T4 with IS Output
Entity Drawing TTF300-L3H
XP/IS Class I, Div 1,2 Group ABCD T6,T4 with IS Output
Entity Drawing TTF300-L3H
Zone 1 AEx/Ex db [ia Ga] IIC T6...T1 Gb
cFMus Explosion Proof and Intrinsically safe
Model TTF300-L7H (L1H +L3H) for USA,
Model TTF300-R7H (R1H + R3H) for Canada
From HW-Rev.: 02.00
Control Drawing
XP Class I, Div 1,2 Group ABCD T6,T4 for Conduit Um <= 42VDC 32mA fused
DIP Class II, Div 1,2 Group EFG T6,T4 Um <= 42VDC 32mA fused
XP/IS Class I, Div 1,2 Group ABCD T6,T4 with IS Output
Entity Drawing TTF300-L3H
IS Class I,II,III Div 1,2 Group ABCDEFG T6,T4 with
Entity Drawing TTF300-L1H
Zone 1 AEx/Ex db [ia Ga] IIC T6...T1 Gb

Transmitter Ex marking FM / CSA

a
FM Intrinsically Safe
Model TTF300-L1H
Up to HW-Rev.: 01.07
TTF300-L1H
Control Drawing
Model TTF300-L1P
Control Drawing
Model TTF300-L1F
Control Drawing
Class I, Div. 1 + 2, Groups A, B, C, D
Class I, Zone 0, AEx ia IIC T6
FM Non-Incendive
TTF300-L2H
Model TTF300-L2H
Up to HW-Rev.: 01.07
Control Drawing
Model TTF300-L2P
Control Drawing
Model TTF300-L2F
Control Drawing
TTF300-L3H
Class I, Div. 2, Groups A, B, C, D
Class I Zone 2 Group IIC T6
FM Explosion proof
Model TTF300-L3
XP, DIP Class I, II, III, Div. 1 + 2, Groups A-G, factory sealed
TTF300-L3H, TTF300-L1H
SAP_214832
TTF300-L1..P (IS)
TTF300-L1..F (IS)
SAP_214830 (NI_PS)
SAP_214828 (NI_AA)
TTF300-L2..P (NI_PS)
TTF300-L2..P (NI_AA)
TTF300-L2..F (NI_PS)
TTF300-L2..F (NI_AA)