Engine Functions; Engine Sequences; Engine Start Functions; Start Sequence - Deif SGC 120 User Manual

Single genset controller
Hide thumbs Also See for SGC 120:
Table of Contents

Advertisement

6. Engine functions

6.1

Engine sequences

The engine start and stop sequences are started automatically if AUTO mode is selected. In manual mode, the operator has
to initiate the sequences.
6.2

Engine start functions

6.2.1

Start sequence

The following drawing shows the start sequence of the genset.
Configure the run coil timer to activate the fuel relay output and the idle mode output before pre-heat is completed.
Timers
Timers > Cranking
Parameter
Crank Hold Time
Crank Rest Time
Manual Start Delay
Auto Start Delay
User manual 4189341340A EN
Range
1 to 255 s
2 to 60 s
0 to 300s
0 to 43200 s
Default
5 s
5 s
3 s
3 s
Page 54 of 76

Advertisement

Table of Contents
loading

Table of Contents