No.
Output source
20
Dig In F
21
Dig In G
22
Dig In H
23
Dig In I
24
Emergency stop
25
Stop solenoid
26
Fail to start
27
Fail to stop
28
Fuel relay
29
Gen available
30
L1 phase OV shutdown
31
L1 phase UV shutdown
32
L2 phase OV shutdown
33
L2 phase UV shutdown
34
L3 phase OV shutdown
35
L3 Phase UV Shutdown
36
Gen over current
37
High engine coolant temp
38
Low fuel LVL
39
Low LOP
40
Mains high volt
41
Mains low volt
42
Oil pressure open circuit
43
Open gen contactor
44
Open mains contactor
45
Over freq shutdown
46
Over speed shutdown
User manual 4189341340A EN
Description
This output is activated when digital input F is activated.
This output is activated when digital input G is activated.
This output is activated when digital input H is activated.
This output is activated when digital input I is activated.
This output is activated when the emergency stop is activated.
This output is activated when the stop solenoid output is high.
This output is activated when the fail to start alarm is activated.
This output is activated when the fail to stop alarm is activated.
This output is activate when the fuel relay is active.
This output is activated when the timer for the warm-up delay expires.
This output is activated when the over-voltage shutdown alarm for phase L1
is activated.
This output is activated when the under-voltage shutdown alarm for phase
L1 is activated.
This output is activated when the over-voltage shutdown alarm for phase
L2 is activated.
This output is activated when the under-voltage shutdown alarm for phase
L2 is activated.
This output is activated when the over-voltage shutdown alarm for phase
L3 is activated.
This output is activated when the under-voltage shutdown alarm for phase
L3 is activated.
This output is activated when the controller shuts down the genset
because of over-current.
This output is activated when the alarm for high engine temperature is
activated.
This output is activated when the low fuel alarm is activated.
This output is activated when the low LOP alarm is activated.
This output is activated when the mains voltage is more than the
configured value.
This output is activated when the mains voltage is less than the configured
value.
This output is activated when the alarm for oil pressure (open circuit) is
activated.
This output is activated when:
• The close mains/open genset input is activated or
• When the load is transferred to the mains in AMF mode.
This output is activated when:
• The close genset/open mains input is activated or
• When the load is transferred to the genset.
This output is activated when the shutdown alarm for over-frequency is
activated.
This output is activated when the shutdown alarm for overspeed is
activated.
Page 73 of 76