Parameter
(Digital) Activation
Delay
((DIG) ACTIVATION
DELAY)
(LOP) Circuit Fault
Action
(OPEN CKT ALARM)
(LOP) Lube Oil
Pressure Sensor
Calibration
Analogue Input 4 (LOP/DIG I)
Parameter
Use Input As
(SENSOR SELECTION)
(Digital) Source
((DIG) SOURCE)
Name
(NAME)
(Digital) Polarity
((DIG) POLARITY)
(Digital) Action
((DIG) ACTION)
(Digital) Activation
((DIG) ACTIVATION)
(Digital) Activation
Delay
((DIG) ACTIVATION
DELAY)
(LOP) Circuit Fault
Action
(OPEN CKT ALARM)
(LOP) Lube Oil
Pressure Sensor
Calibration
User manual 4189341340A EN
Range
From Monitoring On
Always
1 to 60 s
None
Notification
Warning
Electrical Trip
Shutdown
Resistance: 10 to 100
Ω
Pressure: 1.0 to 10.0
bar
Range
Not used
Digital Input I
S4 Sensor (4-20 mA
LOP)
See Digital input
source selection in
this document
Auxiliary Input I
Close to Activate
Open to Activate
None
Notification
Warning
Electrical Trip
Shutdown
Never
From Engine Start
From Monitoring On
Always
1 to 60 s
None
Notification
Warning
Electrical Trip
Shutdown
Current: 4 to 20 mA
Pressure: 0.0 to 10.0
bar
Default
1 s
None
-
Default
Not used
Not used
-
Close to Activate
None
From Monitoring On
1 s
None
-
Description
If the input is active when the timer expires, the
controller actives the action for the digital input.
Configure the action for an open circuit failure.
Configure the resistance and pressure values
for the 10 measurement points in the calibration
table.
Description
Select what to use the input as.
Select the source from the list.
You can configure the name of the input.
Select the polarity for the input.
Select the action when the input is activated.
Configure from when the digital input is
monitored.
If the input is active when the timer expires, the
controller actives the action for the digital input.
Configure the action for an open circuit failure.
Configure the current and pressure values for
the 10 measurement points in the calibration
table.
Page 25 of 76