Parameter
Crank Disconnect At
Alt Frequency
(ALT FREQUENCY)
Crank Disconnect At
Engine Speed
(ENGINE SPEED)
Disconnect On
Charging Alt Voltage
(DISC ON CHG ALT
VOLT)
Charging Alt
Disconnect Volt
Threshold
(CHG ALT
THRESHOLD)
Speed Monitoring (SPEED MONITOR)
Parameter
Engine Speed Sense
Source
(SPEED SENSE
SOURCE)
Flywheel Teeth
(Magnetic Pickup)
W-Point Frequency @
1500
Under-speed
Shutdown
(UNDER SPEED
SHUTDOWN)
Under-speed
Threshold
(UNDER SPEED
THRESH)
Under-speed Delay
(UNDER SPEED
DELAY)
Over-speed Threshold
(OVER SPEED
THRESH)
Over-speed Delay
(OVER SPEED DELAY)
Gross Over-speed
Threshold
(GROSS OS
THRESHOLD)
Initial Low Speed
User manual 4189341340A EN
Range
10 to 70 Hz
150 to 4000 RPM
Enable
Disable
5.0 to 30.0 V
Range
Alternator frequency
Magnetic Pickup
W-Point Frequency
1 to 300
0 to 500
Enable
Disable
0 to 3600 RPM
1 to 60 s
700 to 4000 RPM
1 to 20 s
100 to 200 %
500 to 1800 RPM
Default
20 Hz
600 RPM
Not enabled
5.0 V
Default
Alternator frequency
110
274
Not enabled
1400 RPM
3 s
1600 RPM
3 s
130 %
1100 RPM
Description
If the frequency is more than this set point
during cranking, the controller disconnects the
crank.
If the engine speed is more than this set point
during cranking, the controller disconnects the
crank.
If the charging alternator voltage is more than
the alternator set point (CHG ALT THRESHOLD)
during cranking attempts, the cranks is
disconnected.
If the charging alternator voltage is more than
this set point during cranking, the cranks is
disconnected.
Description
Configure how engine speed is monitored.
The number of teeth on the flywheel.
The frequency at the W-point of the charging
alternator.
If this parameter is enabled, the controller shuts
down the engine when the speed is less than
the configured set point for under-speed.
When the speed is less than this set point, the
controller shuts down the engine.
If the speed is still less than the under-speed
set point when the timer expires, the engine
shuts down.
The set point for over-speed.
If the speed is still more than the over-speed
set point when the timer expires, the controller
activates an alarm.
If the speed is more than this set point, the
engine shuts down. The percentage is of the
nominal speed.
Use this parameter to reduce the amount of
pollution when the engine starts. This is the
initial speed of the engine, and is lower than the
operating speed.
Page 34 of 76