Parameter
Idle to Rated Delay
Time
Start-up Idle Mode
Time
Stopping Idle Time
Idle Mode Pulse Time
Battery Monitoring (BATTERY MONITOR)
Parameter
Low Battery Voltage
Action
(LOW VOLT ACTION)
Low Battery Voltage
Threshold
(LOW VOLT
THRESHOLD)
Low Battery Voltage
Delay
(LOW VOLT DELAY)
High Battery Voltage
Action
(HIGH VOLT ACTION)
High Battery Voltage
Threshold
(HIGH VOLT
THRESHOLD)
High Battery Voltage
Delay
(HIGH VOLT DELAY)
Charging Alternator Monitoring (CHARGE ALT MON)
Parameter
Charging Alternator
Fail Action
(FAIL ACTION)
Charging Alternator
Fail Threshold
(FAIL THRESHOLD)
Charging Alternator
Fail Delay
User manual 4189341340A EN
Range
0 to 1200 s
0 to 1200 s
0 to 1200 s
0 to 60 s
Range
None
Notification
Warning
Electrical Trip
Shutdown
8.0 to 31.0 V
5 to 1800 s
None
Notification
Warning
Electrical Trip
Shutdown
9.0 to 32.0 V
5 to 1800 s
Range
None
Notification
Warning
Electrical Trip
Shutdown
0.0 to 35.0 V
5 to 60 s
Default
10 s
10 s
10 s
2 s
Default
None
8.0 V
30 s
None
15 V
30 s
Default
None
10.0 V
10 s
Description
Time for the engine to go from idle speed to
rated speed.
The engine operates at low speed for this time
duration. You can configure the low speed with
the Initial Low Speed parameter.
In idle mode, the engine operates at low speed
for this time duration before the engine shuts
down.
The pulse time for the idle mode output.
Description
Configure the action for when the battery
voltage is low.
The action for low battery voltage is activated
when the voltage load is less than this set
point.
If the battery voltage is less than the low
voltage set point (LOW VOLT THRESHOLD)
when the timer expires, the controller activates
the action for low battery voltage.
Configure the action for when the battery
voltage is high.
The action for high battery voltage is activated
when the voltage load is more than this set
point.
If the battery voltage is more than the set point
for high voltage (HIGH VOLT THRESHOLD)
when the timer expires, the controller activates
the action for high battery voltage.
Description
Configure the action for charging alternator
failure.
The action for charging alternator failure is
activated when the alternator voltage is more
than this set point.
If the alternator voltage is more than the set
point for high voltage (FAIL THRESHOLD) when