Deif SGC 120 User Manual page 72

Single genset controller
Hide thumbs Also See for SGC 120:
Table of Contents

Advertisement

No.
Source
15
V-belt broken switch
16
Neutral SW signal
17
Regeneration SW inhibit signal
18
Mains contactor latched
19
Gen contactor latched
20
Idle mode enable
21
Alternate nominal switch
9.2
Digital outputs
No.
Output source
1
Disable
2
Sounder alarm
3
Battery over volt
4
Battery under volt
5
Charge alt shutdown
6
Charge alt warning
7
Close gen contactor
8
Close mains contactor
9
Mains failure
10
Common alarm
11
Common electrical trip
12
Common shutdown
13
Common warning
14
Cooling down
15
Dig In A
16
Dig In B
17
Dig In C
18
Dig In D
19
Dig In E
User manual 4189341340A EN
Description
• Mains monitoring is enabled and there is a mains failure. The input is
deactivated. The is still a mains failure and the mains breaker opens.
When this input is activated an alarm is shown on the display. You can
configure the alarm type.
This input is for CAN bus.
This input is for CAN bus.
When this input is activated, the mains breaker closes and the genset
breaker opens.
When this input is activated, the genset breaker closes and the mains
breaker opens.
You can activate idle mode with this input.
If this input is activated, the default nominal settings switch to the
alternative nominal settings.
Description
The output is not used.
This output is high when an alarm is generated. The output is active for the
duration of the alarm.
This output is activated when there is an active alarm for battery over-
voltage.
This output is activated when there is an active alarm for battery under-
voltage.
This output is activated when there is an active shutdown alarm for charge
failure.
This output is activated when there is an active warning alarm for charge
failure.
This output is activated when the digital input for close genset/open mains
is activated in manual mode.
This output is activated when the digital input for close mains/open genset
is activated in manual mode.
This output is activated when there is a mains failure.
This output is activated when one of the alarm types is activated.
This output is activated when there is an active electrical trip alarm.
This output is activated when there is an active shutdown alarm.
This output is activated when there is an active warning alarm.
This output is activated when the cooldown period of the genset is
initiated. The output is activate for the duration of the period.
This output is activated when digital input A is activated.
This output is activated when digital input B is activated.
This output is activated when digital input C is activated.
This output is activated when digital input D is activated.
This output is activated when digital input E is activated.
Page 72 of 76