Parameter
(FAIL DELAY)
Preheating (PREHEAT)
Parameter
Pre-heat Timer
(PREHEAT TIMER)
Engine Temperature
(ENG TEMP EN)
Engine Temperature
Threshold
(ENG TEMP LIMIT)
Coolant Control
Parameter
Enable (coolant
control)
Temperature Control
ON Threshold
OFF Threshold
Automatic Fuel Transfer (AFT FUNCTION)
Parameter
AFT Activation
Threshold
(AFT ACT
THRESHOLD)
AFT deactivation
threshold
(AFT DEACT
THRESHOLD)
Timeout After
Activation
(TIMEOUT AFTER ACT)
Monitor AFT From
Engine On (MON AFT
ON ENG ON)
User manual 4189341340A EN
Range
Range
1 to 900 s
Enable
Disable
10 to 300 °C
Range
Enable
Disable
Heater Control
Cooler Control
0 to 250 °C
0 to 250 °C
Range
0 to 99 %
1 to 100 %
1 to 1200 s
Enable
Disable
Default
Default
10 s
Not enabled
25 °C
Default
Not enabled
Heater Control
50 °C
50 °C
Default
40 %
80 %
600 s
Not enabled
Description
the timer expires, the controller activates the
action for charging alternator failure.
Description
When the pre-heat timer expires, the engine
starts to crank.
If this parameter is enabled, the pre-heat
output is deactivated when the engine coolant
temperature is more than the set point for the
coolant temperature (ENG TEMP LIMIT).
The set point for the engine coolant
temperature.
Description
Enable this parameter to configure the coolant
control.
Select the type of coolant control.
Cooler control: If the cooler temperature is
more than the ON threshold, the output for
Coolant Temperature Control is activated.
Heater control: If the heater temperature is less
than the ON threshold, the output for Coolant
Temperature Control is activated.
Cooler control: If the cooler temperature is less
than the OFF threshold, the output for Coolant
Temperature Control is deactivated.
Heater control: If the heater temperature is
more than the OFF threshold, the output for
Coolant Temperature Control is deactivated.
Description
If the fuel level is less than this threshold, the
auto fuel transfer output is activated.
If the fuel level is more than this threshold, the
output for auto fuel transfer is deactivated.
If the fuel level is less than the deactivation
threshold when this timer expires, the controller
activates a timeout alarm and deactivates the
fuel transfer output.
If this parameter is enabled, the controller
monitors the fuel level when the engine is
running.
Page 36 of 76