FARE / FRE MODULE

1 Aux. DC OUT +24 V
2 Aux. DC OUT GND
3 FARE - Activation OUT
4 FARE - Ground OUT
5 FARE - Acknowledge IN
1 2 3 4 5
6 7 8 9 10
6 FRE - NO (energized closed)
7 FRE - C
8 FRE - Fault IN
9 Key Safe - Activation OUT
10 Key Safe - Ground OUT
FARE / FRE
The FARE / FRE Module (HOP-406-100) is an input/
output module used to connect to Fire Alarm Routing
Equipment (FARE), Fault Routing Equipment (FRE)
and Key Safe Adapter. The module provides a 24 V DC
Auxiliary output to power the connected equipment.
The module route Fire and Fault signals to the external
equipment.
FARE / FRE Module is colour coded Blue
Dimensions H-130 mm x W-28 mm x D-117 mm
Auxiliary power 24 V DC ± 5 % at 1 A maximum
2 A maximum
shared between all Modules in the panel
Interface to FARE equipment (DIN14675)
FARE Output is monitored for short and open circuit
Notifier INSPIRE E10/E15 Control Panels - Installation instructions
DE
3 x 10KΩ
I/O
FIRE/FAULT ROUTING
Dark Blue
Interface to FRE equipment (e.g. Dialler)
FRE input is supervised for open and short circuit
Interface to Key Safe Adapter for Key Safe (VdS2105)
the Module can be given an identification label
FARE CONFIGURATION
Where the module is used for FARE application you
can give it a label, set it with 'Confirmation Input
Required', with Output settings to include 'Reference
Measurement (ohms)' and option to 'Remain in
Service'.
FRE CONFIGURATION
Where the module is used for FRE application you can
give it a label, set it with 'Confirmation Input', 'Fault
Input' or 'No Input'.
KEY SAFE CONFIGURATION
Where the module is used for Key Safe application,
then you can give it a Key Safe label and option to
select 'Key Safe required'.
INDICATORS
Green LED
Lit - Power On, Unlit - Power Off
Blinking - when registration, Initialisation or
upgrade process is active.
Yellow LED
Lit - Common fault at module, Unlit - No fault