Indicator
Alarm
indicator
Fault
indicator
Functions
The power module consists of a power factor correction (PFC) rectifier and
inverter. It performs AC/DC or DC/DC conversion on the mains and battery inputs,
and stabilizes the bus voltage. The inverter (DC/AC) converts the inputs into sine
wave outputs.
Specifications
Issue 05 (2023-07-10)
Color
Status
Blinking
at short
interval
s
Off
Yellow
Steady
on
Off
Red
Steady
on
Off
Dimensions (H x W x D): 86 mm x 442 mm x 620 mm
Weight: < 21 kg
Rated output capacity: 30 kVA/30 kW
Power density: 20.64 W/inch
Copyright © Huawei Digital Power Technologies Co., Ltd.
Description
The module is not configured, the inverter or
rectifier software is being upgraded, or the
inverter software is being upgraded (blinking
at 4 Hz, on for 0.125s and off for 0.125s).
The rectifier software is being upgraded.
A minor alarm is generated for the inverter or
rectifier.
There is no minor alarm for the inverter or
rectifier, or the rectifier software is being
upgraded.
A critical alarm is generated for the inverter or
rectifier.
There is no critical alarm for the inverter or
rectifier, or the rectifier software is being
upgraded.
3
2 Product Overview
32