UPS5000-E-(30 kVA-120 kVA)-FM
User Manual
Table 3-2 Power cable terminal requirements
Port
Mains
input
Bypass
input
Battery
input
Output
PE
Table 3-3 Recommended upstream input and downstream output circuit breakers
UPS Capacity
30 kVA
60 kVA
Issue 05 (2023-07-10)
When the mains input and bypass input share a power source, configure input
power cables as mains input power cables. In addition, cables listed in
3-1
apply only to the following conditions:
The cables are installed along the wall or on the floor (IEC-60364-5-52 C
standards).
The ambient temperature is 30°C.
The AC voltage loss is less than 3%, and the DC voltage loss is less than
1%. The recommended cable diameters in
through-current requirements. Users should evaluate the line voltage loss
based on the actual cable length. If the voltage loss exceeds the
requirements, increase the cable diameter properly.
Single- or multi-core 90°C-resistant copper flexible cables are used.
Connection
Method
Crimped OT
terminals
Crimped OT
terminals
Crimped OT
terminals
Crimped OT
terminals
Crimped OT
terminals
Copyright © Huawei Digital Power Technologies Co., Ltd.
Bolt
Bolt Hole
Specifications
Diameter
M10
11 mm
M10
11 mm
M12
13 mm
M10
11 mm
M10
11 mm
Component
Mains input circuit
breaker
Bypass input circuit
breaker
Downstream output
circuit breaker
Mains input circuit
breaker
Bypass input circuit
breaker
3 Installation
Table 3-1
meet the basic
Bolt Length
30 mm
30 mm
35 mm
30 mm
30 mm
a
Specifications
63 A/3P
63 A/3P
63 A/3P
125 A/3P
125 A/3P
Table
Torque
26 N·m
26 N·m
46 N·m
26 N·m
26 N·m