UPS5000-E-(30 kVA-120 kVA)-FM
User Manual
Old Web
1.
2.
Issue 05 (2023-07-10)
Figure 4-7 Running Parameter
NO TE
Click Submit after setting parameters on the WebUI.
On the WebUI, choose Monitoring > Parameter Settings > System Settings,
and set Paral. sys. hibernate to Enable.
Set Module cycle hiber. period (d) to an integer ranging from 1 to 100. The
default value is 30.
Figure 4-8 Running Parameter
NO TE
Click Submit after setting parameters on the WebUI.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 Single UPS Commissioning
109