UPS5000-E-(30 kVA-120 kVA)-FM
User Manual
Item
Battery
input
(lead-
acid
battery)
Ground
cable
Issue 05 (2023-07-10)
Nominal discharge
current (A)
Maximum discharge
current (A)
Recommende
d cross-
sectional area
2
(mm
)
Recommende
d cross-
sectional area
2
(mm
)
When selecting, connecting, and routing power cables, follow local safety
regulations and rules.
When the external conditions change, for example, the cable layout or
ambient temperatures, perform verification in accordance with the
IEC-60364-5-52 or the local regulations.
If the rated voltage is 400 V, multiply the currents by 0.95. If the rated voltage
is 415 V, multiply the currents by 0.92.
When the primary loads are non-linear loads, increase the cross-sectional
areas of the neutral wires 1.5–1.7 times.
The nominal battery discharge current refers to the current of forty 12 V
batteries at 480 V in standard configuration.
The maximum battery discharge current refers to the current when forty 12 V
batteries in standard configuration, that is, two hundred and forty 2 V battery
cells (1.67 V/cell), stop discharging.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Specifications
30 kVA
N
(When
the UPS
connect
s to a
non-
linear
load,
increase
the
cross-
section
al
area.)
66
79
+
3 x 16
N
-
PE
10
3 Installation
60 kVA
90 kVA
132
197
158
236
3 x 50
3 x 70
16
35
120 kVA
263
315
3 x 120
50
60

Advertisement

Table of Contents
loading

Table of Contents