Installation; Dip Switch Settings - Security Tronix ST-PTZ650FM-23X Installation Manual

Indoor flush mount ptz camera
Table of Contents

Advertisement

Installation

DIP Switch Settings

Preparation
Before installation, make sure that the protocol, baud rate and address code used by the
product is fully consistent with the PTZ control device. The corresponding DIP switch diagram
can be seen below:
Address Settings
DIP switch SW1 is for the address settings of camera. OFF status means 0 while ON status
means 1.
(See illustration above) Turn on the 1st and 3rd (allocated to ON position) and get the binary
code 00000101, so the correspondence address is 5.
Detailed settings please refer to the back "Address Code Mapping Table"(appendix Ⅳ ).
Baud Rate Settings
The 4th and 5th DIP Switches of the "FUN SW 2" set the Baud rate. Factory-default setting is
2400bps.
Baud rate: 1200bps 、 2400bps 、 4800bps 、 9600bps selectable. See next page for DIP switch
settings.