7 Installation
7.5.3
To fill the water circuit
1 Connect the water supply hose to the fill valve.
2 Open the fill valve.
3 Make sure that the automatic air purge valve is open (at least 2
turns).
INFORMATION
For  location  of  the  air  purge  valve,  see  Components:
Indoor unit in chapter "15 Technical data" on page 72.
4 Fill  the  circuit  with  water  until  the  manometer  indicates  a
pressure of ±2.0 bar.
5 Purge as much air as possible from the water circuit.
6 Close the fill valve.
7 Disconnect the water supply hose from the fill valve.
NOTICE
The  water  pressure  indicated  on  the  manometer  will  vary
depending  on  the  water  temperature  (higher  pressure  at
higher water temperature).
However,  at  all  times  water  pressure  shall  remain  above
1 bar to avoid air entering the circuit.
7.5.4
To fill the domestic hot water tank
1 Open  every  hot  water  tap  in  turn  to  purge  air  from  the  system
pipe work.
2 Open the cold water supply valve.
3 Close all water taps after all air is purged.
4 Check for water leaks.
5 Manually  operate  the  field  installed  pressure  relief  valve  to
ensure that free water flow through the discharge pipe.
7.5.5
To insulate the water piping
The  piping  in  the  complete  water  circuit  MUST  be  insulated  to
prevent condensation and reduction of the heating capacity.
If  the  temperature  is  higher  than  30°C  and  the  humidity  is  higher
than  RH  80%,  the  thickness  of  the  sealing  materials  should  be  at
least 20 mm to prevent condensation on the surface of the sealing.
7.5.6
To connect the recirculation piping
1 Loosen and remove the screws at the bottom of the unit.
2 Slide the front panel of the unit downwards and remove it.
3 Loosen and remove the 4 screws that fix the top panel.
4 Remove the top panel from the unit.
Installer reference guide
34
3
4x
4
2
2x
1
5 Remove the expansion vessel.
6 Remove the upper insulation cover of the unit.
a
Knock­out hole
b
Connection for recirculation piping
7 Remove the knock­out hole at the backside of the unit.
8 Connect  the  recirculation  piping  to  the  recirculation  connection
and route the piping through the knock­out hole at the backside
of the unit.
9 Remove the indicated part in the figure below.
10 Re­attach the insulation, expansion vessel and casing.
ERLQ004~008CA + EHVH04+08S18CA3VF
a
b
Daikin Altherma low temperature split
4P366226­1 – 2014.01