Daikin Altherma ERLQ004CAV3 Installer's Reference Manual page 57

Hide thumbs Also See for Altherma ERLQ004CAV3:
Table of Contents

Advertisement

3x
#
Code
N/A
[E­08]
Power saving function for outdoor unit:
▪ 0: Disabled
▪ 1 (default): Enabled
Power consumption control
See 
"5  Application  guidelines"  on  page 
about this functionality.
#
Code
[A.6.3.1]
[4­08]
Mode:
▪ 0 (No limitation)(default): Disabled.
▪ 1  (Continuous):  Enabled:  You  can
set  one  power  limitation  value  (in  A
or  kW)  to  which  the  system  power
consumption will be limited for all the
time.
▪ 2  (Digital  inputs):  Enabled:  You  can
set  up  to  four  different  power
limitation  values  (in  A  or  kW)  to
which 
consumption will be limited when the
corresponding digital input asks.
[A.6.3.2]
[4­09]
Type:
▪ 0 (Current): The limitation values are
set in A.
▪ 1  (Power)(default):  The  limitation
values are set in kW.
[A.6.3.3]
[5­05]
Value: Only applicable in case of full
time power limitation mode.
0~50 A, step 1 A (default: 50 A)
[A.6.3.4]
[5­09]
Value: Only applicable in case of full
time power limitation mode.
0~20 kW, step 0.5 kW (default: 20 kW)
Amp. limits for DI: Only applicable in case of power limitation mode
based on digital inputs and based on current values.
[A.6.3.5.1]
[5­05]
Limit DI1
0~50 A, step 1 A (default: 50 A)
[A.6.3.5.2]
[5­06]
Limit DI2
0~50 A, step 1 A (default: 50 A)
ERLQ004~008CA + EHVH04+08S18CA3VF
Daikin Altherma low temperature split
4P366226­1 – 2014.01
1 2 3
Description
10  for  detailed  information
Description
the 
system 
power
#
Code
[A.6.3.5.3]
[5­07]
Limit DI3
0~50 A, step 1 A (default: 50 A)
[A.6.3.5.4]
[5­08]
Limit DI4
0~50 A, step 1 A (default: 50 A)
kW limits for DI: Only applicable in case of power limitation mode
based on digital inputs and based on power values.
[A.6.3.6.1]
[5­09]
Limit DI1
0~20 kW, step 0.5 kW (default: 20 kW)
[A.6.3.6.2]
[5­0A]
Limit DI2
0~20 kW, step 0.5 kW (default: 20 kW)
[A.6.3.6.3]
[5­0B]
Limit DI3
0~20 kW, step 0.5 kW (default: 20 kW)
[A.6.3.6.4]
[5­0C]
Limit DI4
0~20 kW, step 0.5 kW (default: 20 kW)
Average timer
The  average  timer  corrects  the  influence  of  ambient  temperature
variations.  The  weather­dependent  set  point  calculation  is  done  on
the average outdoor temperature.
The outdoor temperature is averaged over the selected time period.
#
Code
[A.6.4]
[1­0A]
Outdoor average timer:
▪ No averaging (default)
▪ 12 hours
▪ 24 hours
▪ 48 hours
▪ 72 hours
Offset temperature external outdoor ambient sensor
Only  applicable  in  case  of  an  external  outdoor  ambient  sensor  is
installed and configured.
You can calibrate the external outdoor ambient temperature sensor.
It is possible to give an offset to the thermistor value. The setting can
be  used  to  compensate  for  situations  where  the  external  outdoor
ambient sensor cannot be installed on the ideal installation location
(see installation).
#
Code
[A.6.5]
[2­0B]
−5~5°C, step 0.5°C (default: 0°C)
Forced defrost
You can manually start a defrost operation.
The decision to execute the manual defrost operation is made by the
outdoor  unit  and  depends  on  ambient  and  heat  exchanger
conditions.  When  the  outdoor  unit  accepted  the  forced  defrost
operation,    will  be  displayed  on  the  user  interface.  If    is  NOT
displayed  within  6  minutes  after  forced  defrost  operation  was
enabled, the outdoor unit ignored the forced defrost request.
#
Code
[A.6.6]
N/A
Do you want to start a defrost operation?
▪ OK
▪ Cancel
8 Configuration
Description
Description
Description
Description
Installer reference guide
57