12 Troubleshooting
12

Troubleshooting

12.1
General guidelines
Before  starting  the  troubleshooting  procedure,  carry  out  a  thorough
visual  inspection  of  the  unit  and  look  for  obvious  defects  such  as
loose connections or defective wiring.
WARNING
▪ When  carrying  out  an  inspection  on  the  switch  box  of
the unit, always make sure that the unit is disconnected
from the mains. Turn off the respective circuit breaker.
▪ When a safety device was activated, stop the unit and
find  out  why  the  safety  device  was  activated  before
resetting  it.  NEVER  bridge  safety  devices  or  change
their  values  to  a  value  other  than  the  factory  default
setting.  If  you  are  unable  to  find  the  cause  of  the
problem, call your dealer.
DANGER: RISK OF ELECTROCUTION
WARNING
Prevent  hazard  due  to  the  inadvertent  resetting  of  the
thermal  cut­out:  this  appliance  must  NOT  be  supplied
through  an  external  switching  device,  such  as  a  timer,  or
connected to a circuit that is regularly turned ON and OFF
by the utility.
DANGER: RISK OF BURNING
Installer reference guide
66
12.2
Solving problems based on
symptoms
12.2.1
Symptom: The unit is NOT heating as
expected
Possible causes
The temperature setting is NOT
correct
The water flow is too low
The water volume in the
installation is too low
12.2.2
Symptom: The compressor does NOT
start (space heating or domestic water
heating)
Possible causes
The unit must start up out of its
operation range (the water
temperature is too low)
ERLQ004~008CA + EHVH04+08S18CA3VF
Corrective action
Check the temperature setting on
the remote controller. Refer to
the operation manual.
Check and make sure that:
▪ All shut­off valves of the water
circuit are completely open.
▪ The water filter is clean. Clean
if necessary.
▪ There  is  no  air  in  the  system.
Purge  air  if  necessary.  You
can  purge  air  manually  (see
"9.3.1 To perform a manual air
purge" on page 61) or use the
automatic  air  purge  function
(see 
"9.3.2  To  perform  an
automatic  air  purge"  on  page
62).
▪ The water pressure is >1 bar.
▪ The  expansion  vessel  is  NOT
broken.
▪ The  resistance  in  the  water
circuit  is  NOT  too  high  for  the
pump 
(see 
"15.7 
ESP
curve" on page 98).
If the problem persists after you
have conducted all of the above
checks, contact your dealer. In
some cases, it is normal that the
unit decides to use a low water
flow.
Make sure that the water volume
in the installation is above the
minimum required value (see
"6.3.3 To check the water
volume" on page 22).
Corrective action
If the water temperature is too
low, the unit uses the backup
heater to reach the minimum
water temperature first (15°C).
Check and make sure that:
▪ The  power  supply  to  the
backup  heater  is  correctly
wired.
▪ The  backup  heater  thermal
protector is NOT activated.
▪ The  backup  heater  contactors
are NOT broken.
If the problem persists after you
have conducted all of the above
checks, contact your dealer.
Daikin Altherma low temperature split
4P366226­1 – 2014.01