To Perform An Automatic Air Purge; To Interrupt Air Purge; To Perform A Test Run; To Perform An Actuator Test Run - Daikin Altherma ERLQ004CAV3 Installer's Reference Manual

Hide thumbs Also See for Altherma ERLQ004CAV3:
Table of Contents

Advertisement

9 Commissioning
Tue
Air purge
Manual
Speed
Low
Circuit
SHC
No
Stop
5 Use the   and   buttons to scroll to Speed.
6 Use the   and   buttons to set the desired pump speed.
Result: Low
Result: High
7 If  applicable,  set  the  desired  position  of  the  3­way  valve.  Use
the   and   buttons to scroll to Circuit.
8 Use  the    and    buttons  to  set  the  desired  position  of  the  3­
way valve.
Result: SHC
Result: Tank
9 Set  the  desired  position  of  the  bypass  valve.  Use  the    and 
buttons to scroll to .
10 Use  the    and    buttons  to  set  the  desired  position  of  the
bypass valve.
Result: No (boiler not bypassed)
Result: Yes (boiler bypassed)
Result: The air purge function automatically stops after 42 minutes.
9.3.2
To perform an automatic air purge
1
Set the user permission level to Installer. See "To set the user
permission level to Installer" on page 42.
2 Set the air purge mode: go to [A.7.3.1] 
Commissioning > Air purge > Type.
3 Select Automatic and press 
4 Go  to  [A.7.3.4] 
  >  Installer  settings  >  Commissioning  >  Air
purge  >  Start  air  purge  and  press 
function.
Result: Air purging will start and the following screen will be shown.
Tue
Air purge
Automatic
Speed
Low
Circuit
SHC
Yes
Stop
Result: The air purge function automatically stops after 42 minutes.
9.3.3
To interrupt air purge
1 Press 
  and  press 
  to  confirm  the  interruption  of  the  air
purge function.
9.4
To perform a test run
Prerequisite: Make sure the user interface shows the home screens
and  that  the  space  heating  and  domestic  hot  water  demands  are
turned off.
1 Go  to  [A.7.1]: 
  >  Installer  settings  >  Commissioning  >  Test
run.
2 Select a test and press 
. Example: Heating.
3 Select OK and press 
.
Result:  The  test  run  starts.  It  stops  automatically  when  done
(±30 min). To stop it manually, press 
Installer reference guide
62
01:18
 > Installer settings >
.
  to  start  the  air  purge
01:18
, select OK and press 
.
INFORMATION
If  2  user  interfaces  are  present,  you  can  start  a  test  run
from both user interfaces.
▪ The  user  interface  used  to  start  the  test  run  displays  a
status screen.
▪ The  other  user  interface  displays  a  "busy"  screen.  You
cannot stop the test run as long as the "busy" screen is
shown.
If  the  installation  of  the  unit  has  been  done  correctly,  the  unit  will
start up during test operation in the selected operation mode. During
the  test  mode,  the  correct  operation  of  the  unit  can  be  checked  by
monitoring  leaving  water  temperature  and  tank  temperature
(domestic hot water mode).
To  monitor  the  temperature,  go  to  [A.6]  and  select  the  information
you want to check.
9.5
To perform an actuator test run
Purpose  of  the  actuator  test  run  is  to  confirm  the  operation  of  the
different actuators (e.g., when you select pump operation, a test run
of the pump will start).
Prerequisite: Make sure the user interface shows the home screens
and  that  the  space  heating  and  domestic  hot  water  demands  are
turned off.
1 Make  sure  the  room  temperature  control,  the  leaving  water
temperature  control  and  the  domestic  hot  water  control  are
turned OFF via the user interface.
2 Go  to  [A.7.4]: 
  >  Installer  settings  >  Commissioning  >
Actuator test run.
3 Select an actuator and press 
4 Select OK and press 
.
Result:  The  actuator  test  run  starts.  It  automatically  stops  when
finished. To stop it manually, press 
9.5.1
Possible actuator test runs
▪ Backup heater test
▪ Pump test
INFORMATION
Calibration  of  the  produced  heat  calculation  is  included  in
this test.
Make sure that air is purged before executing the test run.
Also avoid causing disturbances in the water circuit during
the test run.
▪ 2­way valve test
▪ 3­way valve test
▪ Bivalent signal test
▪ Alarm output test
▪ Heating signal test
▪ Quick heat­up test
▪ Circulation pump test
ERLQ004~008CA + EHVH04+08S18CA3VF
. Example: Pump.
, select OK and press 
.
Daikin Altherma low temperature split
4P366226­1 – 2014.01