5 Application guidelines
5.4
Setting up the domestic hot water
tank
5.4.1
System layout – Integrated DHW tank
UI
a
b c
d
f
h
h
M
e
g
a
Outdoor unit
b
Indoor unit
c
Heat exchanger
d
Backup heater
e
Pump
f
Motorised 3­way valve
g
DHW tank
h
Shut­off valve
i
Collector (field supply)
FHL1...3
Under floor heating
UI
User interface
5.4.2
Selecting the volume and desired
temperature for the DHW tank
People  experience  water  as  hot  when  its  temperature  is  40°C.
Therefore, the DHW consumption is always expressed as equivalent
hot  water  volume  at  40°C.  However,  you  can  set  the  DHW  tank
temperature at a higher temperature (example: 53°C), which is then
mixed with cold water (example: 15°C).
Selecting  the  volume  and  desired  temperature  for  the  DHW  tank
consists of:
1
Determining  the  DHW  consumption  (equivalent  hot  water
volume at 40°C).
2
Determining  the  volume  and  desired  temperature  for  the  DHW
tank.
Possible DHW tank volumes
Type
Integrated DHW tank
Energy saving tips
▪ If the DHW consumption differs from day to day, you can program
a weekly schedule with different desired DHW tank temperatures
for each day.
▪ The  lower  the  desired  DHW  tank  temperature,  the  more  cost
effective.  By  selecting  a  larger  DHW  tank,  you  can  lower  the
desired DHW tank temperature.
▪ The heat pump itself can produce domestic hot water of maximum
55°C  (50°C  if  outdoor  temperature  is  low).  The  electrical
resistance  integrated  in  the  heat  pump  can  higher  this
temperature.  However,  this  consumes  more  energy.  Daikin
recommends  to  set  the  desired  DHW  tank  temperature  below
55°C to avoid using the electrical resistance.
Installer reference guide
16
i
FHL1
FHL2
FHL3
Possible volumes
180 l
▪ The higher the outdoor temperature, the better the performance of
the heat pump.
▪ If  energy  prices  are  the  same  during  the  day  and  the  night,
Daikin recommends to heat up the DHW tank during the day.
▪ If energy prices are lower during the night, Daikin recommends
to heat up the DHW tank during the night.
▪ When the heat pump produces domestic hot water, it cannot heat
up  a  space.  When  you  need  domestic  hot  water  and  space
heating at the same, Daikin recommends to produce the domestic
hot  water  during  the  night  when  there  is  lower  space  heating
demand.
Determining the DHW consumption
Answer the following questions and calculate the DHW consumption
(equivalent  hot  water  volume  at  40°C)  using  the  typical  water
volumes:
Question
How many showers are needed
per day?
How many baths are needed per
day?
How much water is needed at the
kitchen sink per day?
Are there any other domestic hot
water needs?
Example: If the DHW consumption of a family (4 persons) per day is
as follows:
▪ 3 showers
▪ 1 bath
▪ 3 sink volumes
Then the DHW consumption = (3×100 l)+(1×150 l)+(3×10 l)=480 l
Determining the volume and desired temperature for the DHW
tank
Formula
V
=V
+V
×(T
−40)/(40−T
)
1
2
2
2
1
V
=V
×(40−T
)/(T
−T
)
2
1
1
2
1
V
DHW consumption (equivalent hot water volume at 40°C)
1
V
Required DHW tank volume if only heated once
2
T
DHW tank temperature
2
T
Cold water temperature
1
5.4.3
Setup and configuration – DHW tank
▪ For  large  DHW  consumptions,  you  can  heat  up  the  DHW  tank
several times during the day.
▪ To heat up the DHW tank to the desired DHW tank temperature,
you can use the following energy sources:
▪ Thermodynamic cycle of the heat pump
▪ Electrical backup heater
▪ For more information about optimizing the energy consumption for
producing domestic hot water, see "8 Configuration" on page 41.
ERLQ004~008CA + EHVH04+08S18CA3VF
Typical water volume
1 shower = 10 min×10 l/min =
100 l
1 bath = 150 l
1 sink = 2 min×5 l/min = 10 l
Example
If:
▪ V
=180 l
2
▪ T
=54°C
2
▪ T
=15°C
1
Then V
=280 l
1
If:
▪ V
=480 l
1
▪ T
=54°C
2
▪ T
=15°C
1
Then V
=307 l
2
Daikin Altherma low temperature split
4P366226­1 – 2014.01