Daikin Altherma ERLQ004CAV3 Installer's Reference Manual page 15

Hide thumbs Also See for Altherma ERLQ004CAV3:
Table of Contents

Advertisement

Setup
▪ Integrate the auxiliary boiler as follows:
a
b c d e
g
f
M
f
n
m
a
Outdoor unit
b
Indoor unit
c
Heat exchanger
d
Backup heater
e
Pump
f
Shut­off valve
g
Motorised 3­way valve (delivered with DHW tank)
h
Non­return valve (field supply)
i
Shut­off valve (field supply)
j
Collector (field supply)
k
Auxiliary boiler (field supply)
l
Aquastat valve (field supply)
m
DHW tank
n
Heat exchanger coil
FHL1...3
Under floor heating
NOTICE
▪ Make sure the auxiliary boiler and its integration in the
system complies with applicable legislation.
▪ Daikin  is  NOT  responsible  for  incorrect  or  unsafe
situations in the auxiliary boiler system.
▪ Make  sure  the  return  water  to  the  heat  pump  does  NOT  exceed
55°C. To do so:
▪ Set  the  desired  water  temperature  via  the  auxiliary  boiler
controller to maximum 55°C.
▪ Install  an  aquastat  valve  in  the  return  water  flow  of  the
heat pump.
▪ Set the aquastat valve to close above 55°C and to open below
55°C.
▪ Install non­return valves.
▪ Make sure to only have one expansion vessel in the water circuit.
An expansion vessel is already premounted in the indoor unit.
▪ Install the digital I/O PCB (option EKRP1HB).
▪ Connect  X1  and  X2  (changeover  to  external  heat  source)  on  the
PCB to the auxiliary boiler thermostat.
To setup the heat emitters, see "5.2 Setting up the space heating
system" on page 10.
ERLQ004~008CA + EHVH04+08S18CA3VF
Daikin Altherma low temperature split
4P366226­1 – 2014.01
h
j
h
i
k
l
i
FHL1
FHL2
FHL3
5 Application guidelines
Configuration
Via the user interface (quick wizard):
▪ Set the use of a bivalent system as external heat source.
▪ Set the bivalent temperature and hysteresis.
NOTICE
▪ Make  sure  the  bivalent  hysteresis  has  enough
differential  to  prevent  frequent  changeover  between
indoor unit and auxiliary boiler.
▪ Because  the  outdoor  temperature  is  measured  by  the
outdoor unit air thermistor, install the outdoor unit in the
shadow so that it is NOT influenced or turned ON/OFF
by direct sunlight.
▪ Frequent  changeover  may  cause  corrosion  of  the
auxiliary  boiler.  Contact  the  manufacturer  of  the
auxiliary boiler for more information.
Changeover to external heat source decided by an auxiliary
contact
▪ Only  possible  in  external  room  thermostat  control  AND  one
leaving  water  temperature  zone  (see 
heating system" on page 10).
▪ The auxiliary contact can be:
▪ An outdoor temperature thermostat
▪ An electricity tariff contact
▪ A manually operated contact
▪ ...
▪ Setup: Connect the following field wiring:
L
H
Com
Indoor/Auto/Boiler
A
K1A
K2A
N
B
Boiler thermostat input
TI
A
Auxiliary contact (normal closed)
H
Heating demand room thermostat (optional)
K1A
Auxiliary relay for activation of indoor unit (field supply)
K2A
Auxiliary relay for activation of boiler (field supply)
Indoor
Indoor unit
Auto
Automatic
Boiler
Boiler
NOTICE
▪ Make sure the auxiliary contact has enough differential
or time delay to prevent frequent changeover between
indoor unit and auxiliary boiler.
▪ If  the  auxiliary  contact  is  an  outdoor  temperature
thermostat, install the thermostat in the shadow so that
it  is  NOT  influenced  or  turned  ON/OFF  by  direct
sunlight.
▪ Frequent  changeover  may  cause  corrosion  of  the
auxiliary  boiler.  Contact  the  manufacturer  of  the
auxiliary boiler for more information.
"5.2  Setting  up  the  space
Indoor
B TI
X2M
1 2 3 4
X Y
K1A
K2A
Installer reference guide
15