To Fill The Water Circuit; To Protect The Water Circuit Against Freezing - Daikin EBLA16D V3 Installation Manual

Hide thumbs Also See for EBLA16D V3:
Table of Contents

Advertisement

a
b
a
Water OUT (screw connection, male, 1")
b
Water IN (screw connection, male, 1")
c
Shut-off valve with integrated filter (delivered as
accessory)(2× screw connection, female, 1")
d
Thread sealant
2 Connect the field piping to the shut-off valve.
3 Connect the field piping to the outdoor unit water outlet.
NOTICE
About the shut-off valve with integrated filter (delivered as
accessory):
▪ The installation of the valve at the water inlet is
mandatory.
▪ Mind the flow direction of the valve.
NOTICE
For service purposes, it is recommended to also install a
shut-off valve and drain point to the water OUT connection.
This shut-off valve and drain point are field supplied.
NOTICE
Install air purge valves at all local high points.
NOTICE
In case an optional domestic hot water tank is installed: A
pressure relief valve (field supply) with an opening
pressure of maximum 10  bar (=  1  MPa) must be installed
on the domestic cold water inlet connection in accordance
with the applicable legislation.
5.2.2

To fill the water circuit

To fill the water circuit, use a field supply filling kit. Make sure you
comply with the applicable legislation.
EBLA09~16D + EDLA09~16D
Daikin Altherma 3 M
4P620239-1B – 2022.05
b
1
d
2
c
NOTICE
For models with integrated backup heater: The unit
contains an automatic air purge valve on the backup
heater. Make sure it is open. All automatic air purge valves
in the system (in the unit, and in the field piping –if any)
must remain open after commissioning.
For other models: The unit contains a manual air purge
valve. Make sure it is closed. Only open it when performing
an air purge.
5.2.3
To protect the water circuit against
freezing
About freeze protection
Frost can damage the system. To prevent the hydraulic components
from freezing, the software is equipped with special frost protection
functions such as water pipe freeze prevention and drain prevention
(see the installer reference guide) that include the activation of pump
in case of low temperatures.
However, in case of a power failure, these functions cannot
guarantee protection.
Do one of the following to protect the water circuit against freezing:
▪ Add glycol to the water. Glycol lowers the freezing point of the
water.
▪ Install freeze protection valves. Freeze protection valves drain the
water from the system before it can freeze. Insulate the freeze
protection valves in a similar way as the water piping, but do NOT
insulate the inlet and outlet (release) of these valves.
NOTICE
If you add glycol to the water, do NOT install freeze
protection valves. Possible consequence: Glycol leaking
out of the freeze protection valves.
NOTICE
If you add glycol to the water, you also need to install a
flow switch (EKFLSW1).
Freeze protection by glycol
About freeze protection by glycol
Adding glycol to the water lowers the freezing point of water.
WARNING
Ethylene glycol is toxic.
5 Piping installation
Installation manual
19