7.4
Connecting the refrigerant piping
DANGER: RISK OF BURNING
CAUTION
▪ Do NOT use mineral oil on flared part.
▪ Do NOT reuse piping from previous installations.
▪ NEVER  install  a  drier  to  this  R410A  unit  to  guarantee
its  lifetime.  The  drying  material  may  dissolve  and
damage the system.
NOTICE
Take  the  following  precautions  on  refrigerant  piping  into
account:
▪ Avoid  anything  but  the  designated  refrigerant  to  get
mixed into the refrigerant cycle (e.g. air).
▪ Only use R410A when adding refrigerant.
▪ Only use installation tools (e.g. manifold gauge set) that
are  exclusively  used  for  R410A  installations  to
withstand the pressure and to prevent foreign materials
(e.g.  mineral  oils  and  moisture)  from  mixing  into  the
system.
▪ Install  the  piping  so  that  the  flare  is  NOT  subjected  to
mechanical stress
▪ Protect the piping as described in the following table to
prevent dirt, liquid or dust from entering the piping.
▪ Use  caution  when  passing  copper  tubes  through  walls
(see figure below).
Unit
Installation period
Outdoor unit
>1 month
<1 month
Indoor unit
Regardless of the
period
INFORMATION
Do  NOT  open  the  refrigerant  stop  valve  before  checking
the refrigerant piping. When you need to charge additional
refrigerant  it  is  recommended  to  open  the  refrigerant  stop
valve after charging.
Take the following guidelines into account when connecting pipes:
▪ Coat  the  flare  inner  surface  with  ether  oil  or  ester  oil  when
connecting  a  flare  nut.  Tighten  3  or  4  turns  by  hand,  before
tightening firmly.
▪ Always use two wrenches together when loosening a flare nut.
▪ Always  use  a  spanner  and  torque  wrench  together  to  tighten  the
flare nut when connecting the piping. This to prevent nut cracking
and leaks.
ERLQ004~008CA + EHVH04+08S18CA3VF
Daikin Altherma low temperature split
4P366226­1 – 2014.01
a
d
Piping size
7.4.1
Use  a  pipe  bender  for  bending.  All  pipe  bends  should  be  as  gentle
as possible (bending radius should be 30~40 mm or larger).
7.4.2
1 Cut the pipe end with a pipe cutter.
2 Remove burrs with the cut surface lacing downward so that the
Protection method
a
Pinch the pipe
Pinch or tape the pipe
3 Remove the flare nut from the stop valve and put the flare nut
4 Flare  the  pipe.  Set  exactly  at  the  position  as  shown  in  the
A
5 Check that the flaring is properly made.
a
b
c
a
Torque wrench
b
Spanner
c
Piping union
d
Flare nut
Tightening
(mm)
torque (N•m)
Ø6.4
15~17
Ø15.9
63~75
Pipe bending guidelines
To flare the pipe end
CAUTION
▪ Incomplete flaring may cause refrigerant gas leakage.
▪ Do  NOT  re­use  flares.  Use  new  flares  to  prevent  for
refrigerant gas leakage.
▪ Use  flare  nuts  that  are  included  with  the  unit.  Using
different  flare  nuts  may  cause  to  refrigerant  gas
leakage.
chips does not enter the pipe.
b
a
Cut exactly at right angles.
b
Remove burrs.
on the pipe.
following illustration.
A
Conventional flare tool
Flare tool for
Clutch type
R410A (clutch
(Ridgid-type)
type)
0~0.5 mm
1.0~1.5 mm
b
c
a
Flare's inner surface must be flawless.
b
The pipe end must be evenly flared in a perfect circle.
c
Make sure the flare nut is lifted.
7 Installation
Flare
Flare shape
dimensions
(mm)
(mm)
90° ±2
8.7~9.1
19.3~19.7
A
R=0.4~0.8
Wing nut type
(Imperial-type)
1.5~2.0 mm
Installer reference guide