5 Application guidelines
a
Remote controller of the heat pump convectors
b
User interface
c
Mixing valve station
d
Pressure regulating valve
INFORMATION
A pressure regulating valve should be implemented before
the  mixing  valve  station.  This  is  to  guarantee  the  correct
water  flow  balance  between  the  main  leaving  water
temperature  zone  and  the  additional  leaving  water
temperature  zone  in  relation  to  the  required  capacity  of
both water temperature zones.
▪ For the main zone:
▪ A mixing valve station is installed before the under floor heating.
▪ The  pump  of  the  mixing  valve  station  is  controlled  by  the  ON/
OFF signal on the indoor unit (X2M/5 and X2M/7; normal closed
shut­off valve output).
▪ The room temperature is controlled by the user interface, which
is used as room thermostat.
▪ For the additional zone:
▪ The heat pump convectors are directly connected to the indoor
unit.
▪ The desired room temperature is set via the remote controller of
the heat pump convectors for each room.
▪ The heating demand signals of each heat pump convector are
connected  in  parallel  to  the  digital  input  on  the  indoor  unit
(X2M/1 and X2M/4). The indoor unit will only supply the desired
additional  leaving  water  temperature  when  there  is  an  actual
demand.
▪ The user interface connected to the indoor unit decides the space
operation  mode.  Mind  that  the  operation  mode  on  each  remote
controller  of  the  heat  pump  convectors  must  be  set  to  match  the
indoor unit.
Configuration
Setting
Unit temperature control:
▪ #: [A.2.1.7]
▪ Code: [C­07]
Number of water temperature
zones:
▪ #: [A.2.1.8]
▪ Code: [7­02]
In case of heat pump convectors:
External room thermostat for the
additional zone:
▪ #: [A.2.2.5]
▪ Code: [C­06]
Shut­off valve output
At the mixing valve station
Installer reference guide
14
Value
2 (RT control): Unit operation is
decided based on the ambient
temperature of the user interface.
Note: 
▪ Main  room  =  user  interface
used  as  room  thermostat
functionality
▪ Other  rooms  =  external  room
thermostat functionality
1 (2 LWT zones): Main +
additional
1 (Thermo ON/OFF): When the
used external room thermostat or
heat pump convector can only
send a thermo ON/OFF
condition.
Set to follow the thermo demand
of the main zone.
Set the desired main leaving
water temperature.
Benefits
▪ Comfort.
▪ The  smart  room  thermostat  functionality  can  decrease  or
increase  the  desired  leaving  water  temperature  based  on  the
actual room temperature (modulation).
▪ The  combination  of  the  two  heat  emitter  systems  provides  the
excellent  heating  comfort  of  the  under  floor  heating,  and  the
rapid  air  heat  up  of  the  heat  pump  convectors  (e.g.,  living
room=under  floor  heating  and  the  bedroom=convector  (no
continuous heating)).
▪ Efficiency.
▪ Depending  on  the  demand,  the  indoor  unit  supplies  different
leaving  water  temperature  matching  the  design  temperature  of
the different heat emitters.
▪ Under floor heating has the best performance with Altherma LT.
5.3
Setting up an auxiliary heat source
for space heating
▪ Space heating can be done by:
▪ The indoor unit
▪ An auxiliary boiler (field supply) connected to the system
▪ When the room thermostat requests heating, the indoor unit or the
auxiliary  boiler  starts  operating  depending  on  the  outdoor
temperature  (status  of  the  changeover  to  external  heat  source).
When  the  permission  is  given  to  the  auxiliary  boiler,  the  space
heating by the indoor unit is turned OFF.
▪ Bivalent  operation  is  only  possible  for  space  heating,  NOT  for
domestic  hot  water  production.  Domestic  hot  water  is  always
produced by the DHW tank connected to the indoor unit.
INFORMATION
▪ During  heating  operation  of  the  heat  pump,  the
heat pump operates to achieve the desired temperature
set  via  the  user  interface.  When  weather­dependent
operation is active, the water temperature is determined
automatically depending on the outdoor temperature.
▪ During  heating  operation  of  the  auxiliary  boiler,  the
auxiliary  boiler  operates  to  achieve  the  desired  water
temperature set via the auxiliary boiler controller.
ERLQ004~008CA + EHVH04+08S18CA3VF
Daikin Altherma low temperature split
4P366226­1 – 2014.01