▪ For the additional zone:
▪ The heat pump convectors are directly connected to the indoor
unit.
▪ The desired room temperature is set via the remote controller of
the heat pump convectors for each room.
▪ The heating or cooling demand signals of each heat  pump
convector are connected in parallel to the digital input on the
indoor unit (X2M/35 and X2M/30). The indoor unit will only
supply the desired additional leaving water temperature when
there is an actual demand.
▪ The user interface connected to the indoor unit decides the space
operation mode. Mind that the operation mode on each remote
controller of the heat  pump convectors must be set to match the
indoor unit.
Configuration
Setting
Unit temperature control:
▪ #: [2.9]
▪ Code: [C-07]
Number of water temperature
zones:
▪ #: [4.4]
▪ Code: [7-02]
In case of heat pump convectors:
External room thermostat for the
additional zone:
▪ #: [3.A]
▪ Code: [C-06]
Shut-off valve output
Shut-off valve
At the mixing valve station
Benefits
▪ Comfort.
▪ The smart room thermostat functionality can decrease or
increase the desired leaving water temperature based on the
actual room temperature (modulation).
▪ The combination of the two heat emitter systems provides the
excellent heating comfort of the under  floor heating, and the
excellent cooling comfort of the heat pump convectors.
▪ Efficiency.
▪ Depending on the demand, the indoor unit supplies different
leaving water temperature matching the design temperature of
the different heat emitters.
▪ Under floor heating has the best performance with Altherma LT.
EPGA11~16DAV3 + EABH/X16DA6V+9W
Daikin Altherma – Low temperature split
4P556069-1 – 2018.10
Value
2 (Room thermostat): Unit
operation is decided based on
the ambient temperature of the
user interface.
Note:
▪ Main room = user interface
used
as
room
thermostat
functionality
▪ Other rooms = external room
thermostat functionality
1 (Dual zone): Main + additional
1 (1 contact): When the used
external room thermostat or
heat pump convector can only
send a thermo ON/OFF
condition. No separation between
heating or cooling demand.
Set to follow the thermo demand
of the main zone.
If the main zone must be shut off
during cooling mode to prevent
condensation on the floor, set it
accordingly.
Set the desired main leaving
water temperature for heating
and/or cooling.
5 Application guidelines
5.3
Setting up an auxiliary heat source
for space heating
▪ Space heating can be done by:
▪ The indoor unit
▪ An auxiliary boiler (field supply) connected to the system
▪ When the room thermostat requests heating, the indoor unit or the
auxiliary boiler starts operating depending on the outdoor
temperature (status of the changeover to external heat source).
When the permission is given to the auxiliary boiler, the space
heating by the indoor unit is turned OFF.
▪ Bivalent operation is only possible for space heating, NOT for
domestic hot water production. Domestic hot water is always
produced by the DHW tank connected to the indoor unit.
INFORMATION
▪ During heating operation of the heat  pump, the
heat  pump
operates
temperature set via the user interface. When weather-
dependent operation is active, the water temperature is
determined automatically depending on the outdoor
temperature.
▪ During heating operation of the auxiliary boiler, the
auxiliary boiler operates to achieve the desired water
temperature set via the auxiliary boiler controller.
Setup
▪ Integrate the auxiliary boiler as follows:
NOTICE
▪ Make sure the auxiliary boiler and its integration in the
system complies with applicable legislation.
▪ Daikin is NOT responsible for incorrect or unsafe
situations in the auxiliary boiler system.
▪ Make sure the return water to the heat  pump does NOT exceed
55°C. To do so:
▪ Set the desired water temperature via the auxiliary boiler
controller to maximum 55°C.
▪ Install an aquastat valve in the return water flow of the
heat pump. Set the aquastat valve to close above 55°C and to
open below 55°C.
▪ Install non-return valves.
▪ Make sure to only have one expansion vessel in the water circuit.
An expansion vessel is already pre-mounted in the indoor unit.
▪ Install the digital I/O PCB (option EKRP1HB).
▪ Connect X1 and X2 (changeover to external heat source) on the
digital I/O PCB to the auxiliary boiler thermostat.
▪ To setup the heat emitters, see
cooling system" on
page 10.
Configuration
Via the user interface (quick wizard):
▪ Set the use of a bivalent system as external heat source.
▪ Set the bivalent temperature and hysteresis.
Changeover to external heat source decided by an auxiliary
contact
▪ Only possible in external room thermostat control AND one
leaving water temperature zone (see
heating/cooling system" on
page 10).
to
achieve
the
desired
"5.2 Setting up the space heating/
"5.2  Setting up the space
Installer reference guide
15