Installing Mini-Slot Interface Wiring And Connections - Eaton 9E Generation 3 Installation And Operation Manual

20–30 kva (208/220v)
Hide thumbs Also See for 9E Generation 3:
Table of Contents

Advertisement

UPS System Installation
k.
Install the power terminal cover right and left sides using the provided hardware.
4.
Route and install RJ-45 Controller Area Network (CAN) cables between the UPS cabinets. See Figure
Figure 4-11 and Figure 4-17 for wiring information.
5.
Route and install pull chain wiring between the UPS cabinets and cabinet MOBs. See Figure 4-11,
Figure 4-16, and Figure 4-17 for wiring information.
6.
Reinstall the interface terminal cover using the retained hardware.
7 .
If wiring Mini-Slot connections, proceed to paragraph 4.11.3; otherwise, proceed to Step 8.
8.
Install the power terminal cover top using the provided hardware (see Figure 4-9).
9.
Install the power terminal cover right and left sides using the provided hardware.
10. Proceed to paragraph 4.13.

4.11.3 Installing Mini-Slot Interface Wiring and Connections

NOTE
For installation and setup of an Mini-Slot card, contact an Eaton service representative (see paragraph 1.7)
To install wiring:
1.
If not already installed, install the LAN drop.
2.
Route and install the LAN and other cables to the appropriate Mini-Slot cards. See Figure 4-10 and
Figure 4-11 for Mini-Slot communication bay locations.
3.
Refer to the manual supplied with the Mini-Slot card for operator instructions.
4.
Install the power terminal cover top using the provided hardware (see Figure 4-9).
5.
Install the power terminal cover right and left sides using the provided hardware.
6.
Proceed to paragraph 4.13.
4-18
Eaton 9E UPS (20–30 kVA, 208/220V) Generation 3 Installation and Operation Manual P-164000301—Rev 1
LAN drop for use with Mini-Slot cards must be provided by the customer.