Product Specifications; Specifications; Electrical Specifications; Environmental Specifications - Eaton SPM Series Installation And Operation Manual

System parallel module
Table of Contents

Advertisement

Chapter 7 Product Specifications
This section provides the following specifications:
Model Numbers
Environmental and safety specifications
7 .1

Specifications

The following sections detail the SPM specifications and the environmental and safety specifications for the
SPM. Environmental and Safety Specifications.
7 .1 .1 Electrical
7 .1 .2 Environmental
specifications
Basic Unit rating
Input and output voltage
Max. current of MBS
Max. current of MIS
Max. current of MOB
specifications
operating Temperature①
Storage Temperature①
Transit Temperature①
humidity
Enclosure Class per IEC 60529
rohS/WEEE
operating Altitude ②
① The recommended operational, storage and transit temperature with CSB and C&D batteries is
generally max. 25°C. Please refer to the battery manufacturer's recommendations for accurate
temperatures.
② Altitude-thermal de-rating as per EN62040-3:2011.
System Parallel Module
Units
kVA
120kVA x 3
Volts
Amps
Amps
Amps
5°C – 40°C
-25°C to 55°C
-25°C to 60°C
5 % to 95 % maximum noncondensing
IP20, Optional 21
Required
Maximum 1000m at 30°C without derating
22
rating 50/60hz
200kVA x 3
415
415
705
1173
654
1086
218
362