These mandatory requirements for installation into a mobile Home, are in addition to those listed under
Residential Installation.
Clearances to combustible surfaces and materials are shown below.
15 3/8"
205mm
390mm
Figure 11: T4 LE Mobile Home Clearances.
Warning: Under no circumstances is this heater to be installed in a makeshift or "temporary" manner. It may
be fired only after the following conditions have been met.
•
DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE.
•
DO NOT INSTALL IN A SLEEPING ROOM.
•
CAUTION: THE STRUCTURAL INTEGRITY OF THE MOBILE HOME FLOOR, WALLS AND CEILING/
ROOF MUST BE MAINTAINED.
•
The stove must be permanently anchored to the floor. Use the holes located in the bottoms of the legs.
•
Outside air supply must be used for Mobile Home installations -
•
This heater must be installed with listed double-wall connector and compatible ULC-S629 or UL-103HT
listed chimney system.
NOTE: Install all chimney components to the connector and chimney manufacturer's installation
requirements. Consult your chimney supplier/manufacturer for installation advice.
Consult local Builing codes and Fire authorities for approval.
ALT 4-LE 040523-28
Mobile Home Installation
Double Wall Flue Connector
8"
8"
205mm
8"
205mm
21 7/8"
555mm
Alcove: Min. Height 7' (2.13m)
Use Only
for Mobile Home
8"
205mm
8"
205mm
Max. Depth 3' (915 m m)
21
5"
18 1/2"
130mm
470mm
5"
130mm
100003978