TZIDC-210, TZIDC-220 DIGITAL POSITIONER | OI/TZIDC-210/TZIDC-220-EN REV. G
... 10 Operation
... Parameter overview

Parameter descriptions

Para-
Display
Function
meter
P1._
STANDARD
P1.0
ACTUATOR
Actuator type
P1.1
AUTO_ADJ
Automatic adjustment
P1.2
TOL_BAND
Tolerance band
P1.3
DEADBAND
DEAD BAND
P1.4
TEST
Test
P1.5*
ADRESS
Bus address
P1.6
EXIT
Return
P2._
SETPOINT
P2.0
P2.1
P2.2
CHARACT
Charact. curve
P2.3
ACTION
Valve action
P2.4
SHUT_CLS
Shut-off value 0%
P2.5
RAMP UP
Set point ramp, up
P2.6
RAMP DN
Set point ramp, down
P2.7
SHUT_OPN
Shut off value 100%
P2.8
EXIT
Return
P3._
ACTUATOR
P3.0
MIN_RGE
Min. of stroke range
P3.1
MAX_RGE
Max. of stroke range
P3.2
ZERO_POS
Zero position
P3.3
EXIT
Return
P4._, P5._
P6._
MAN_ADJ
P6.0
MIN_VR
Min. valve range
P6.1
MAX_VR
Max. valve range
P6.2
ACTUATOR
Actuator type
P6.3
SPRNG_Y2
Spring action (Y2)
P6.4
ADJ_MODE
Auto adjust mode
P6.5
EXIT
Return
P7._
CTRL_PAR
P7.0
KP UP
KP value, up
P7.1
KP DN
KP value, down
P7.2
TV UP
TV value, up
P7.3
TV DN
TV value, down
P7.4
GOPULS UP
Go pulse, up
Actuator type
Autoadjust
Tolerance band
Dead band
Test
Return to operating level
Characteristic curve
Direction of action
Shut-off value 0 %
Setpoint ramp (up)
Setpoint ramp (down)
Shut-off value 100%
Return to operating level
Operating range, min.
Operating range, max.
Zero position
Return to operating level
Operating range, min.
Operating range, max.
Actuator type
Spring action (Y2)
Dead angle 0 %
Return to operating level
KP value (up)
KP value (down)
TV value (up)
TV value (down)
Possible parameter setting
LINEAR, ROTARY
Function
0.30 bis 10.00
0.10 bis 10.00
Function
1 bis 126
Function
LINEAR, 1:25, 1:50, 25:1, 50:1, USERD
DIRECT, REVERSE
OFF, 0.1 to 45.0
0.1 to 999.9
0.1 to 999.9
OFF, 80.0 to 100
Function
0.0 to 100.0
0.0 to 100.0
CLOCKWISE, CTCLOCKWISE
Function
0.0 to 100.0
0.0 to 100.0
LINEAR, ROTARY
CLOCKWISE, CTCLOCKWISE
FULL, STROKE, CTRL_PAR,
ZERO_POS, LOCKED
Function
1.0 to 100.0
1.0 to 100.0
0 to 1000
0 to 1000
0 to 200
Unit
Factory setting
---
LINEAR
---
---
%
0.30
%
0.10
---
---
---
126
---
---
---
---
---
---
---
LINEAR
---
DIRECT
%
OFF
sec
OFF
sec
OFF
%
OFF
---
---
%
0.0
%
100
---
CTCLOCKWISE
---
---
---
---
%
0
%
100
---
LINEAR
---
CTCLOCKWISE
---
FULL
---
NV_SAVE
---
1.0
---
1.0
msec
100
msec
100
msec
0