Mechanical Mounting; General - ABB TZIDC-210 Operating Instructions Manual

Digital positioner
Hide thumbs Also See for TZIDC-210:
Table of Contents

Advertisement

38
TZIDC-210, TZIDC-220 DIGITAL POSITIONER | OI/TZIDC-210/TZIDC-220-EN REV. G
... 6 Installation

Mechanical mounting

General

Figure 6: Operating range
Arrow
1
on the device feedback shaft (position feedback point)
must move between the arrow marks
1 Measuring range
Figure 7: Measuring and operating ranges of the positioner
2
.
2 Operating range
Operating range for linear actuators:
The operating range for linear actuators is maximum ±45°
symmetrically to the longitudinal axis.
The usable span within the operating range is ideally 40°, but at
least 25°. The usable span should run as symmetrically to the
longitudinal axis as possible.
Operating range of rotary actuators:
The usable span is +57° to −57°, which must be entirely within
the measuring range, but does not necessarily need to run
symmetrically to the longitudinal axis.
Note
During installation make sure that the actuator travel or rotation
angle for position feedback is implemented correctly.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tzidc-220

Table of Contents