TZIDC-210, TZIDC-220 DIGITAL POSITIONER | OI/TZIDC-210/TZIDC-220-EN REV. G
Preconditions for safe operation of the positioner
DANGER
Risk of explosion due to hot parts
Hot parts inside the device pose an explosion hazard.
•
Never open the device immediately after switch-off.
•
A waiting time of at least four minutes should be observed
before opening the device.
When using in hazardous areas, observe the following points:
•
Observe the specification and special conditions
applicable for the device in accordance with the relevant
valid certificate.
•
Manipulation of the device in any form by the user is not
permitted. Only the manufacturer or an explosion
protection specialist may modify the device
•
The IP 65 / NEMA 4x IP rating is only achieved if the
splash guard is screwed in place. Operating the unit
without splash guard cap is prohibited.
•
The device may only be operated using instrument air
that is free from oil, water and dust. The use of
flammable gas, oxygen, or oxygen-enriched gas is not
permitted.
•
High / recurring charging processes in gas zones must be
excluded by the operator.
Cable gland
Limited temperature range of the M20 × 1.5 plastic cable gland
for explosion protection variants:
•
The permissible ambient temperature range is
−20 to 80 °C (−4 to 176 °F).
•
When using the cable gland, you need to make sure that
the ambient temperature is within the permissible range
plus 10 K or that they are suited in terms of the minimal
ambient temperature.
•
The cable gland must be installed in the housing with a
tightening torque of 3.8 Nm. When installing the
connection of the cable gland and cable, check for
tightness to ensure that the required IP rating is met.
9