TZIDC-210, TZIDC-220 DIGITAL POSITIONER | OI/TZIDC-210/TZIDC-220-EN REV. G
1 Attachment bracket
Figure 18: Screwing the attachment bracket onto the positioner
Figure 19: Screwing the positioner onto the actuator
Note
After mounting, check whether the operating range of the
actuator matches the measuring range of the positioner, refer to
General on page 38.

7 Electrical connections

Safety instructions

WARNING
Risk of injury due to live parts!
When the housing is open, contact protection is not provided
and EMC protection is limited.
Before opening the housing, switch off the power supply.
The electrical connection may only be established by authorized
specialist personnel.
Notices on electrical connection in this instruction must be
observed; otherwise, electric safety and the IP-rating may be
adversely affected.
Safe isolation of electric circuits which are dangerous if touched
is only guaranteed when the connected devices fulfill the
requirements of EN 61140 (basic requirements for secure
separation).
To ensure safe isolation, install supply lines so that they are
separate from electrical circuits which are dangerous if touched,
or implement additional isolation measures for them.