TZIDC-210, TZIDC-220 DIGITAL POSITIONER | OI/TZIDC-210/TZIDC-220-EN REV. G
ATEX / UKEX – 'Ex i' type of protection
Ex-marking
Ex marking
Marking
II 2 G Ex ia IIC T6/ T4...T1 Gb
II 2 G Ex ib IIC T6/ T4 ...T1 Gb
II 3 G Ex ic IIC T6/T4 ... T1 Gc
Type Examination Test
TÜV 04 ATEX 2702 X
Certificate
Certificate (UKEX)
EMA22UKEX0032X
Type of protection
Intrinsic safety 'i'
Device class
II 2G / II 3G
Standards
EN 60079-0, EN 60079-11
Temperature data
Temperature class
Ambient temperature Ta
T4 to T1
−40 to 85 °C
T6
−40 to 40 °C*
Electric Data
With the 'Intrinsic safety Ex i IIC' type of protection, only for
connection to a certified FISCO power supply unit or a barrier,
i.e., a power supply unit with maximum values according to the
following tables:
Connection to a barrier or power supply unit
Current circuit (terminal)
Electrical information (maximum values)
Signal circuit
Voltage:
(+11 / −12)
Current:
Power:
L
, C
i
Characteristic
curve:
Connection to a FISCO power supply unit
Current circuit (terminal)
Electrical information (maximum values)
Signal circuit
Voltage:
(+11 / −12)
Current:
Power:
L
, C
i
Characteristic
curve:
Current circuit (terminal)
Electrical information (maximum values)
Feedback on the actuator
For maximum values, see EU-Type examination
position using proximity
certificate PTB 00 ATEX 2049 X Pepperl & Fuchs
switches, (Pepperl & Fuchs
Type 2 proximity switches
SJ2-SN)
(Limit1: +51 / −52),
(Limit2: +41 / −42)
Local communication
Only for connection to a programming device
interface (LCI)
using an ABB LCI adapter (Um ≤ 30 V DC) outside
the hazardous area.
24 V
250 mA
1.2 w
Negligible
i
rectangular
17.5 V
17.5 V
380 mA
360 mA
5.32 w
2.52 W
Negligible
i
rectangular
trapezoidal
Special conditions
Before the final installation, the operator decides on the use
of the device, either
as a device with the 'Intrinsically safe Ex i' type of
protection or
as a device with 'Flameproof enclosure Ex d' type of
protection
The operator must permanently mark the selected type of
use on the name plate. Specific ambient conditions, such as
chemical corrosion, must be taken into account when
affixing the permanent mark.
Devices that also meet the requirements for the 'Intrinsic
safety Ex i' type of protection in accordance with a separate
declaration may no longer be operated as intrinsically safe if
they have been previously used in the 'flameproof enclosure
Ex d' type of protection.
Permissible for the 'Natural gas version' only:
The positioner TZIDC-210 may be operated as a power
supply only with gases of Group IIA and temperature class
T1 outdoors or inside of buildings with sufficient
ventilation.
The supplied gas must be free of air and oxygen to
prevent the forming of a hazardous atmosphere.
Exhaust gas must always be discharged outside.
The equipment may only be used as a II 2D type device
TZIDC-210 in areas where the level of mechanical danger is
"low".
For TZIDC-210 electrostatic charging caused by propagating
brush discharge should be prevented when the device is used
for applications involving combustible dust.
For devices that are operated in an intrinsically safe manner,
cable and wire entries should be used that meet the
requirements of EN 60079-11 for Category II 2G as well as the
ambient temperature range.
The 'local communication interface' (LCI) of the TZIDC-210
may only be operated at U
area.
≤ 30 V DC outside the hazardous
m
11