Eac Tr-Cu-012 Ex D - ABB TZIDC-210 Operating Instructions Manual

Digital positioner
Hide thumbs Also See for TZIDC-210:
Table of Contents

Advertisement

28
TZIDC-210, TZIDC-220 DIGITAL POSITIONER | OI/TZIDC-210/TZIDC-220-EN REV. G
... 2 Use in potentially explosive atmospheres
... TZIDC-220 – Ex relevant specification

EAC TR-CU-012 Ex d

Ex marking
Marking
Certificate
Type
Device class
Standards
Temperature data
Device group II 2 G
Temperature class
T4
T5
T6
Electric Data
Voltage
Current
Pneumatic data
Supply pressure
Special conditions
1Ex d IIC T6...Т4 Gb Х
EAC TR-CU-012
TZIDC-220 Doc. 901132
II 2 G
EN 60079-0
EN 60079-1
Ambient temperature Ta
−40 to 85 °C
−40 to 80 °C
−40 to 65 °C
≤ 30 V AC/DC
≤ 20 mA
Standard Version
≤ 6 bar
Marine version
≤ 5.5 bar
Before final installation, the operator needs to decide on the
use of the device, either
A) as a device with 'Ex i' intrinsically safe type of protection
or
B) as a device with 'Ex d' type of protection
and permanently mark the selected type of use on the name
plate. Specific conditions of the surrounding environment,
such as chemical corrosion, must be taken into account when
affixing the permanent mark. Only the manufacturer must
change the selected type of use following a re-examination
Medium strength adhesive must be used to secure the cable
entries and line entries and stop them from twisting and self-
loosening
In the case of high torsional forces, the bearing sleeves must
be replaced due to wear on the shaft for the position pickoff
(significant control deviation).
If the positioner is operated at an ambient temperature
above 60 °C (140 °F) or below −20 °C (−4 °F), make sure to
use cable entries and lines suited for an operating
temperature corresponding to the maximum ambient
temperature increased by 10 K or corresponding to the
minimum ambient temperature, respectively.
The dimensions of the flameproof joint of this equipment
partly exceed the minimum values required by
EN 60079-1:2014 or IEC 60079-1:2014 or partly down-scale the
maximum values required therein. All inquiries relating to
dimensions must be directed to the manufacturer
Screws that comply with the minimum requirements of the
A2-70, A2-80 or 10.12 quality grades must be used to close
the flameproof enclosure.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tzidc-220