7.4.6. High starter voltage alarm

This setting is only available if the Aux input has been set to "Starter battery", see chapter
When enabled, the alarm will activate when the starter battery voltage rises above the set value for more than 10 seconds and
the alarm will deactivate when the starter battery voltage drops below the clear value.
Setting
Set alarm value (setting 41)
Clear alarm value (setting 42)

7.4.7. High temperature alarm

This setting is only available if the Aux input has been set to "temperature", see chapter
When enabled, the alarm will activate when the battery temperature rises above the set value for more than 10 seconds. The
alarm will deactivate when the battery temperature drops below the clear value.
Setting
Set relay value (setting 43)
Clear relay value (setting 44)

7.4.8. Low temperature alarm

This setting is only available if the Aux input has been set to "temperature", see chapter
When enabled, the alarm will activate when the battery temperature falls below the set value for more than 10 seconds. The
alarm will deactivate when the battery temperature rises above the clear value.
Setting
Set relay value (setting 45)
Clear relay value (setting 46)

7.4.9. Midpoint deviation alarm

This setting is only available if the Aux input has been set to "Midpoint"; see chapter
When enabled, the alarm will activate when the midpoint voltage deviation rises above the set value for more than 10 seconds.
The alarm will deactivate when the midpoint voltage deviation drops below the clear value.
Setting
Set alarm value (setting 47)
Clear alarm value (setting 48)

7.5. Display settings

7.5.1. Backlight intensity

The intensity of the backlight This setting ranges from 0 (always off) to 9 (maximum intensity).
Setting
Backlight intensity (setting 49)

7.5.2. Backlight always on

When set the backlight will not automatically turn off after 60 seconds of inactivity.
Page 36
Manual - BMV-712 Smart
Default
1.1 V
1.0 V
Default
0°C
0°F
0°C
0°F
Default
0°C
0°F
0°C
0°F
Default
2 %
1 %
Default
5
Aux input
[40].
Range
Steps
0 - 95.0V
0.1V
0 - 95.0V
0.1V
Aux input
[40].
Range
Step size
-40 - +99°C
1°C
-40 - +210°F
1°F
-40 - +99°C
1°C
-40 - +210°F
1°F
Aux input
[40].
Range
Step size
-40 - +99°C
1°C
-40 - +210°F
1°F
-40 - +99°C
1°C
-40 - +210°F
1°F
Aux input
[40].
Range
Steps
0 - 99 %
1 %
0 - 99 %
1 %
Range
Step size
0 - 9
All features and settings
1