The "clear relay" value needs to be greater than the "set relay" value.
Setting
Set relay value (setting 24)
Clear relay value (setting 25)

7.3.11. Low temperature relay

This setting is available if the aux input has been set to "Temperature", see the
Use the
Temperature unit setting [41]
When the battery temperature drops below the "set relay" value for more than 10 seconds the relay will close.
When the battery temperature rises above the "clear relay" value, the relay will open (after a delay, depending on the
minimum closed time [32]
and/or the
Setting
Set relay value (setting 28)
Clear relay value (setting 29)

7.3.12. Mid voltage relay

This setting is available if the aux input has been set to "Mid point", see the
See the chapter
Midpoint voltage monitoring [46]
When the midpoint voltage deviation rises above the "set relay" value, the relay will close.
When the midpoint voltage deviation falls below the "clear relay" value, the relay will open (after a delay, depending on the
minimum closed time [32]
and/or the
Setting
Set relay value (setting 30)
Clear relay value (setting 31)

7.4. Alarm settings

The BMV battery monitor is equipped with an alarm relay and a buzzer. Alarms are also visible on the VictronConnect app while
connected to the battery monitor or are used to send an alarm signal to a GX device.
Alarms are disabled by default. To enable do the following:
• In the VictronConnect app, enable the alarm by sliding the slider button to the right.
• Via the head unit, enable the alarm by changing the "set" and "clear" value in the alarm settings to any value above zero.

7.4.1. Alarm buzzer

When enabled (set to ON), the buzzer will sound an alarm as soon as an alarm condition occurs. After a button is pressed, the
buzzer will stop sounding.
When disabled (set to OFF) the buzzer will not sound an alarm.
Setting
Alarm buzzer (setting 32)

7.4.2. Low SoC alarm settings

When enabled, the alarm will activate when the state of charge (SoC) falls below the set value for more than 10 seconds. The
alarm will deactivate when the state of charge rises above the clear value
Page 34
Manual - BMV-712 Smart
Default
0V
0V
to choose between °C or °F temperature units.
Relay off delay [32]
settings).
Default
0°C
0°F
0°C
0°F
for more information about the midpoint voltage.
Relay off delay [32]
settings).
Default
0%
0%
Default
Range
0 - 95V
0 - 95V
Aux input [40]
setting.
Range
-40 - +99°C
-40 - +210°F
-40 - +99°C
-40 - +210°F
Aux input [40]
setting.
Range
0 - 99%
0 - 99%
ON
Step size
0.1V
0.1V
Relay
Step size
1°C
1°F
1°C
1°F
Relay
Step size
1%
1%
Modes
ON
OFF
All features and settings