Setting
Set alarm value (setting 33)
Clear alarm value (setting 34)

7.4.3. Low voltage alarm

When enabled, the alarm will activate when the battery voltage falls below the set value for more than 10 seconds. The alarm will
deactivate when the battery voltage rises above the clear value.
Setting
Set alarm value (setting 35)
Clear alarm value (setting 36)

7.4.4. High voltage alarm

When enabled, the alarm will activate when the battery voltage rises above the set value for more than 10 seconds. The alarm
will deactivate when the battery voltage drops below the clear value.
Setting
Set alarm value (setting 37)
Clear alarm value (setting 38)

7.4.5. Low starter voltage alarm

This setting is only available if the Aux input has been set to "Starter battery", see chapter
When enabled, the alarm will activate when the starter battery voltage falls below the set value for more than 10 seconds. The
alarm will deactivate when the starter battery voltage rises above the clear value.
Setting
Set alarm value (setting 39)
Clear alarm value (setting 40)
Page 35
Manual - BMV-712 Smart
Default
1%
1%
Default
1.1V
1.0V
Default
1.1V
1.0V
Default
1.1V
1.0V
Range
Steps
0 - 100%
1%
0 - 100%
1%
Range
Steps
0 - 95.0V
0.1V
0 - 95.0V
0.1V
Range
Steps
0 - 95.0V
0.1V
0 - 95.0V
0.1V
Aux input
[40].
Range
Steps
0 - 95.0V
0.1V
0 - 95.0V
0.1V