is limiting battery current to the maximum current rating.
RTS Open
The Remote Temperature Sensor is not connected to the controller. Use of the RTS is
mended for proper battery charging.
Heatsink Temperature Sensor Open / Shorted
The heatsink temperature sensor is damaged. Return the controller to an authorized Morningstar
dealer for service.
Battery Sense Out of Range / Disconnected
A battery sense wire is disconnected. Inspect the battery sense connections. This alarm is set when
the voltage at the battery sense voltage differs by more than 5 volts from the voltage at the battery
terminals.
Uncalibrated
The controller was not factory calibrated. Return the controller to an authorized Morningstar dealer for
service.
48
Operation

4.6 Inspection and Maintenance

recom-
WARNING: RISK OF ELECTRICAL SHOCK.
NO POWER OR ACCESSORY TERMINALS ARE ELECTRICALLY ISOLATED FROM
DC INPUT, AND MAY BE ENERGIZED WITH HAZARDOUS SOLAR VOLTAGE. UNDER CER-
TAIN FAULT CONDITIONS, BATTERY COULD BECOME OVER-CHARGED. TEST BETWEEN
ALL TERMINALS AND GROUND BEFORE TOUCHING.
AVERTISSEMENT: RISQUE DE CHOC ÉLETRIQUE.
NON ALIMENTATION OU AUX BORNES D'ACCESSOIRES SONT ISOLÉS ÉLEC-
TRIQUEMENT DE L'ENTRÉE DE C.C ET DOIT ÊTRE ALIMENTÉS À UNE TENSION DANGERE-
USE SOLAIRE. SOUS CERTAINES CONDITIONS DE DÉFAILLANCE, LA BATTERIE POURRAIT
DEVENIR TROP CHARGÉE. TEST ENTRE TOUTES LES BORNES ET LA MASSE AVANT DE
TOUCHER.
WARNING: Shock Hazard
Disconnect all power sources to the controller before removing the wiring box
cover. Never remove the cover when voltage exists on the TriStar MPPT 150V power
connections.
AVERTISSEMENT : Risque de décharge électrique
Un moyen de déconnexion de tous les poteaux d'alimentation doit être fourni.
Ceux-ci se déconnecte doit être intégrée dans le câblage fixe. Ouvrir que toutes les source
d'énergie se déconnecte avant de retirer le couvercle de la contrôleur, ou accès au câblage.
Table 4-6 below lists the recommended maintenance schedule to keep your TriStar MPPT 150V
performing optimally.
TriStar MPPT Operator's Manual
49