Service Manual - VCDxxSA
10.
Engineering of Electrical Wring
1. Highlights of electrical wiring installation
All field wiring construction should be finished by
qualified electrician.
Air conditioning equipment should be grounded ac-
cording to the local electrical regulations.
Current leakage protection switch should be in-
stalled.
Do not connect the power wire to the terminal of
signal wire.
When power wire is parallel with signal wire, put
wires to their own wire tube and remain at least
300mm gap.
According to table in indoor part named "the speci-
fication of the power" to choose the wiring, make
sure the selected wiring not small than the date
showing in the table.
Select different colors for different wire according to
relevant regulations.
Do not use metal wire tube at the place with acid or
alkali corrosion, adopt plastic wire tube to replace it.
There must be not wire connect joint in the wire
tube If joint is a must, set a connection box at the
place.
The wiring with different voltage should not be in
one wire tube.
Ensure that the color of the wires of outdoor and
the terminal No. are same as those of indoor unit
respectively.
Table: Minimum Cross-Sectional Area able of Power and
Signal Cables
For North America:
Rated Current of
Appliance (A)
≤ 6
6 - 10
10 - 16
16 - 25
25 - 32
For the other regions:
Rated Current of
Appliance (A)
≤ 6
6 - 10
10 - 16
16 - 25
25 - 32
32 - 45
AWG
18
16
14
12
10
Nominal Cross-Sectional
Area(mm
2
)
0.75
1
1.5
2.5
4
6
10. Engineering of Electrical Wring
2. Specific wiring method
Connection method A:
Refer to the wiring method of internal and external
machine communication and wired controller as follows:
Indoor unit
Wired
controller
R C
L G Y1
B W
Y1/Y2
Wired
controller
Connection method B:
To use a 24V thermostat, you need to refer to the
following wiring:
R C G Y1 Y2 B W
R C G Y1 Y2 B W
W1
W2 E
DH L
24V thermostat
NOTE: The wiring method of the thermostat and
the internal machine refers to the wiring of the non-
communication scheme.
Connection method C:
Non-communication scheme wiring reference
• Wiring for 4H and 2C thermostat
W2
W1/E
O/B
Y2
Y1
G
L
C
R
DH
THERMOSTAT
DH
R
C
L
G
Y1
INDOOR UNIT
S4-2 DIP switch o
Perform disconnection and
short-circuit to achieve
partition, control or dehumidi cation
• Wiring for 3H and 1C thermostat
W1
W2 E
DH
S1 S2
R C Y1 Y2 B W
D
L
S1
S2
Outdoor Unit
Indoor unit
W1
W2 E
DH L
S1 S2
R C Y1 Y2 B W D L
S1 S2
Outdoor Unit
B W
W1 W2
E
R
C
Y1 Y2
B W D
OUTDOOR UNIT
S4-1 DIP switch o
Disconnect and short
circuit to realize heating
segment
L