5. Drainage Pipe Installation
Install the drainage pipe as shown below and take
measures against condensation. Improperly installation
could lead to leakage and eventually wet furniture and
belongings.
5.1 Installation principle
Ensure at least 1/100 slope of the drainage pipe
Adopt suitable pipe diameter
Adopt nearby condensate water discharge
5.2 Key points of drainage water pipe
installation
1. Considering the pipeline route and elevation.
Before installing condensate water pipeline, deter-
mine its route and elevation to avoid intersection
with other pipelines and ensure slope is straight.
2. Drainage pipe selection
The drainage pipe diameter shall not small than the
drain hose of indoor unit
According to the water flowrate and drainage pipe
slope to choose the suitable pipe, the water flow-
rate is decided by the capacity of indoor unit.
Relationship between water flowrate and capacity of
indoor unit
Capacity (kBtu/h)
24
30
36
48
60
According to the above table to calculate the total water
flowrate for the confluence pipe selection.
For horizontal drainage pipe (The following table is for
reference)
Reference
PVC
value of inner
pipe
diameter of
pipe (mm)
PVC25
20
25
PVC32
PVC40
31
40
PVC50
PVC63
51
Attention: Adopt PVC40 or bigger pipe to be the main
pipe.
Water flowrate (l/h)
6
7
8
12
14
Allowable
maximum water
Remark
flowrate (l/h)
Slope
Slope
1/50
1/100
39
27
For branch
pipe
70
50
Could be
125
88
used for
247
175
confluence
473
334
pipe
5. Drainage Pipe Installation
For Vertical drainage pipe (The following table is for
reference)
Reference
PVC
value of inner
pipe
diameter of
pipe (mm)
20
PVC25
25
PVC32
31
PVC40
40
PVC50
51
PVC63
67
PVC75
77
PVC90
Attention: Adopt PVC40 or bigger pipe to be the main
pipe.
3. Individual design of drainage pipe system
The drainage pipe of air conditioner shall be in-
stalled separately with other sewage pipe, rainwater
pipe and drainage pipe in building.
The drainage pipe of the indoor unit with water
pump should be apart from the one without water
pump.
4. Supporter gap of drainage pipe
In general, the supporter gap of the drainage pipe
horizontal pipe and vertical pipe is respectively
1m~1.5m and 1.5m~2.0m.
Each vertical pipe shall be equipped with not less
than two hangers.
Overlarge hanger gap for horizontal pipe shall cre-
ate bending, thus leading to air block.
5. The horizontal pipe layout should avoid converse flow or
bad flow
Allowable
maximum water
Remark
flowrate (l/h)
220
For branch
pipe
410
730
Could be
1440
used for
2760
confluence
5710
pipe
8280