EL 0C (Refrigerant Leakage Detection Diagnosis and Solution)

Description:
Judging the abnormality of the refrigeration system according to the number of compressor stops and the changes in
operating parameters caused by excessive exhaust temperature.
Recommended parts to prepare:
• Indoor PCB
• Additional refrigerant
Troubleshooting and
repair:
Power off, then restart the unit 15 minutes later.
Put your hands in front of the
Check system for leakages.
Are any leakages present?
Charge the refrigerant
appropriately(about 10% of
the nameplate charge)
indoor air outlet.
Is there cool or heat
air blowing out from
indoor air outlet?
NO
NO
NO
Troubleshooting 28
YES
Is T2 loose?
NO
Is T1 too close to
the evaporator
NO
Replace the indoor PCB
Repair the leakage and
YES
recharge the refrigerant.
YES
Ensure proper connections.
YES
Install correctly