7.15 PC 0F
PFC module protection diagnosis and solution)
(
Description: When the voltage signal that IPM send to compressor drive chip is abnormal, the LED displays the failure
code and the AC turns off.
Recommended parts to prepare:
• Connection wires
• Inductance
• Outdoor main PCB
• PFC module
Troubleshooting and repair:
At first test the resistance between every two ports of U, V, W of IPM and P, N. If any result of them is 0 or close to 0, the
IPM is defective. Otherwise, please follow the procedure below:
Check whether the
connecting line between
main board and the PFC
module is connected tightly
Yes
Measure whether the voltage
between P and N is normal
refer to the Index?
No
Check
whether
inductance of PFC module
is good? If the inductance is
good, the resistance of the
two ports is 0
Yes
Replace the PFC module
Connect it tightly, check
No
No
Yes
Replace the outdoor main board
the
No
Replace the inductance
Troubleshooting 39
normal or not
Trouble is solved
Service Manual - VCDxxSA
Yes