Data type definitions
5.1

Single command (SC) / Single-point indiation (SP)

...
Coil / input status register or one bit of a holding register
Figure 5-1
Data typ single command / single-point indication
5.2

Double command (DC) / Double-point indication (DP)

...
Coil status
Figure 5-2
Data type double command / double-point indication
5-2
Range of values:
0 – OFF
1 – ON
Bit x
Bit x+1
SC/SP 1
SC/SP 2
Range of values:
0 (bit 1 = 0 and bit 0 = 0) - „Not applicable" for DP,
1 (bit 1 = 0 and bit 0 = 1) - OFF
2 (bit 1 = 1 and bit 0 = 0) - ON
3 (bit 1 = 1 and bit 0 = 1) - Error status/Intermediate position for DP,
Note
„Not applicable": double-point indication is not configured (not
assigned to a binary input).
The value „11" ist transmitted for intermediate position „00" too.
Bit 1
Bit 0
DC/DP 1
Coil status
register
register
xxxx
xxxx+1
...
Bit x+2
SC/SP 3
not permissible for DC
not permissible for DC
Bit 1
Bit 0
DC/DP 2
Coil status
Coil status
register
register
xxxx+2
xxxx+3
7SJ61/62/63 6MD63 – Modbus
C53000-L1840-C001-01
...