General
Procedure
Siemens
Building Technologies
7.3
Back up data in ACS
ACS accesses the data via Read parameter set (save) and Write parameter set (restore).
Back up bus operator unit data in ACS.
1.
Back up locally in the bus operator unit:
Main menu > Data backup > Local > Save
2.
Read the data using ACS and save in an ACS plant. Prerequisite:
The bus operator unit must exist and be selected in ACS, then:
Applications > Plant engineering... > Read parameter set
Read parameter set automatically takes over and backs up data in ACS.
Restore data in a (new) bus operator unit from ACS plant.
1.
Transfer the backup data to the bus operator unit using ACS. Prerequisite:
The bus operator unit must exist and be selected in ACS, then:
Applications > Plant engineering... > Write parameter set
The data is backed up locally in the bus operator unit: Overwrite any existing local
data.
2.
Restore locally backed up data in the bus operator unit:
Main menu > Data backup > Local > Restore
Restore makes the data again available to the bus operator unit, i.e. access
to the device list, Favorites pages, etc. is again possible.
Bus operator unit RMZ792 Series B
7 Data backup
37/58
CE1P3113en
07.07.2011